1.70 - 180615

15. June 2018

Normal Update

Added Features

  • Add Default-LogJob for AUX Events [T3001]
  • Export Device Trace Data to file AND Added timestamps to device trace data [T3383]
  • Implement Service Recovery Actions [T3321]
  • BACS Current Thresholds introduce [T276/#3059]
  • Added Fahrenheit to Sensor settings/screens [T3041]
  • Added Event Jobs "Switch UPS Outlet" [T3309]
  • Added external 'MGE SNMP Card Ref 66074' as UPS Modelvia SNMP [T3353]
  • Event "UPS Batteries too old, call UPS service" added to UNMS hinzufügen [T3398]
  • Added "Set Battery health Level and Active OutputVoltage" [T1197/#1438]
  • Unify the format of triggers in the EventLog [T3344] and bitmasks Wellknown alarms [T3356]
  • SM_T_H_COM Alarms via SNMP added [T3352]

Changed Functionality

  • Changed some menu icons to improve user interface
  • Moved submenu item 'Webserver' from "System" to "Services" menu
  • Moved service enable/disable panel from "System > General" page to "Services > Setup"
  • Changed default email TCP port from 25 to 587 (today generally used by mail-clients)
  • SMTP: enabled NTLM authentication mechanism and changed default from 'PLAIN' to ANONYMOUS
  • Changed email configuration labels for 'Connection Security' selection: 'if available' is now shown as 'STARTTLS' and 'force encryption' as 'TLS/SSL'

Bug Fixes

  • Bugfix for all modular UPS - when text was entered in "Location" menue, screen was crippled
  • Firmware update notification fixed
  • Bugfix at BACS config value Impedance configuration
  • Disabled unsecure ciphers (sslv3, tlsv1.0) in webserver
  • Error message at opening BACS-Events menue when COM1 set to none fixed [T3371]
  • BACS Modules show red led although no thresholds exceeded [T79/#3306]

OEM customer specific features, changes and fixes

  • OEM 002: AEG $$CBSR4 (Protect Blue): Im Status bei Eco-Mode den Bypass ignorieren [T3401]
  • OEM 002: AEG Protect 3. M, $$GRIPOW, UPS screenfixes [T3347]
  • OEM 002: AEG $$AETSER2: 'UPS Alert History' display fixed [T3407]
  • OEM 002: AEG Remove of UPS-Functions at the 'UPS Control' group [T3393]
  • OEM 003: PILLER "APOSTAR AS IV": “Function“ Remote Control added [T3145]
  • OEM 003: PILLER "APOSTAR AS IV" UPS Statusbar and Output LED changed [T3369]
  • OEM 003: PILLER Test #0111 Eventrecorder error UPS Typ “APOTRANS II<125A” [T3345]
  • OEM 003: PILLER Test #0116 APOSTAR AS IV, page „BATTERY”, measuring remaining time changed [T3374]
  • OEM 004: ONLINE $$PREXTXANTO: Correction of battery values for extension packs [T3348]
  • OEM 004: ONLINE Correction of Batteryvoltage value CVL to CVL_B0 for all devices with external Batterypacks
  • OEM 008: LEGRAND $$TRIMOD screen "UPS Setup" added buttons [T3337]
  • OEM 019: BENNING Enertronic screenchages for 3-3 Phase
  • OEM 022: BORRI Integration of new UPS Type 14 [T3385]
  • OEM 025: ROTON added EVO5 series to their model range
  • OEM 028: AKKUTRONIK $$JBUSDAKER Custom Test added [T3338]
  • OEM 028: AKKUTRONIK $$PRABLER / UPS Function "Buzzer/Beeper on/off" n.a. [T3304]
  • OEM 032: EFFEKTA "THOR Modular 10-900 kVA" + "THOR Modular 10-900 kVA MODBUS" changes in UPS protocol [T3397]
  • OEM 032: EFFEKTA $$XONL12B: Statusbar did show incorrecdt status 'UPS Output Off' [T3388]
  • OEM 036: ABB $$CONCE: Remove 'Set of needed UPSs' restriction for the battery current [T3396]
  • OEM 038: ASTRID modbus addresses for UPS 11 added. Range 200
  • OEM 044: HENKELHAUSE added HEALRT, HEAT, HEAM, HRIC and HRIT series
  • OEM 045: ABLEREX Protocoll extension Q5 [T1909/#2072]
  • OEM 045: WOEHRLE STS Transferswitch Tumel Modbus extension [T3238]
  • OEM 048: TRIATHLON First version for TRIATHLON introduce, Power Unlimited removed
  • OEM 050: CENTIEL $$CENTIEL: False alarms fixed [T3336]
  • OEM 050: CENTIEL $$CENTIEL: Mains Input Frequency for 16.7 HZ modules [T3288]
  • OEM 058: SIEL added KSTAR UPS series as Safepower S and HE
  • OEM 066: AKI fix for DELTA modular UPS als Modulys Green Power 20-360 kVA
  • OEM 070: ASTRID $$EVO5: Added raw modbus values
  • OEM 081: CE+T TSI Bravo, $$CET, Redundancy Lost Event transmits wrong value via SNMP [T3386]
  • OEM 082: SALICRU SPS ATS, $$STSABLER, Buzzer On Button fixed [T3341]
  • OEM 082: SALICRU SLC-10000-TWIN/3 PRO, $$XONL12B showed false statusbar "Output Off" [T3363]
  • OEM 082: SALICRU CUBE3 Alarm-extension for $$MBCUBE and $$MBCUBE2 [T3306]
  • OEM 084: UPS Ltd. PW9000 DPA-150 40kVA $$CONCE UPS Screen display fixed [T3365]
  • OEM 097: POWERALL Mexico $$SALISEC calculation for Berechnung Ausgangs-Scheinleistung (kVA) nicht korrekt [T3349]

1.68 - 180328

28. March 2018

Important Update

Added Features

  • Dual Flashrom detection, the new firmware can now automatically detect which firmware ROM is found [T3057]
  • Add BACS Logfile Export Function [T3023]
  • All OEMs may now replace their logo thru Drag & Drop [T278/#3056]
  • UPS Alert History now downloadable as file [T3216]
  • Added license info on page System > About, Stripped board no. from 'Serial No.' on page System > About.
  • SNMP Passwords now optional visible [T3252]
  • Added more polish translations [T2891]

Bug Fixes

  • At EVENTs Power Restored it is now possible to delay timing actions [T63/#3325]
  • E-Mail (SMTP)change for MS Outlook Server 2016: Enabled NTLM authentication mechanism and changed default from 'PLAIN' to ANONYMOUS
  • User interface optimizations: Inconsistent user menau on pages 'SNMP Agent' [T3268], removed messagebox after update [T280/#3054],
  • Forwarding Screen message at IP configuration change [T2893]
  • Reset admin password did not work with previous version [T3276]
  • Restore from old Backup Files fixed [T3325]
  • RCCMD Job now allows the use of hostnames [T3052]
  • Scheduler job dialog may store invalid cron strings [T3326]
  • UNMS, Email Traps, mailHeartbeatError was not displayed with previous version, fixed with [T3266]
  • UPS Thresholds for 'Output Load' inverted, fixed with [T3293]
  • UPS Custom Thresholds removed invalid menues [T3267] and adds functions [T3311]
  • BACS startup process hangs if the UPS was disabled, fixed with this version [T3239]
  • Scheduler Job Labels for UPS Battery Tests were inconsisten, fixed with [T3242]
  • Smaller fixes in UPS configuration menue [T3246]
  • Wizard: Automatic activation of "Check Firmware Update" deleted previous entries, fixed with [T3263]
  • Menue "system time" in IE11 too small, fixed with [T3299]
  • Menue "power" VA and "load" VA size changed [T3246]
  • Ablerex UPS devices functions missing switching buttons added [T328/#2995]
  • BACS Modules show from time to time a RED led, although now alarm is present. Workaround introduced [T79/#3306]

OEM customer specific features, changes and fixes

  • OEM 003/PILLER: "APOSTAR AS IV": Status Text and Events [T3143] + [T3144]
  • OEM 003/PILLER: "APOSTAR AS IV": Page „BATTERY“ changed, [T3141] operation hours [T3138]
  • OEM 003/PILLER: "APOSTAR AS IV": Page „IN2“, Frequenz [T3139] and Page „DC LINK“ current added [T3140]
  • OEM 003/PILLER: "APOSTAR AS IV": Page “PHASE” [T3142] and changes on synoptic [T3147] + [T3148]
  • OEM 003/PILLER: "APOSTAR AS IV": Change in synoptic [T3146]
  • OEM 003/PILLER: "APOJET T II": Page „OUT2“ fixed [T3275]
  • OEM 003/PILLER: "UNIBLOCK UBT IV": Fix in synoptic [T3274] + [T3298]
  • OEM 003/PILLER: "AP Premium" : Fix in synoptic with Firefox [T3301]
  • OEM 003/PILLER: "APOJET": Fix in synoptic page „OUT2“ [T3279], removed german as language [T3277]
  • OEM 003/PILLER: "APOJET T II / APOJET LVR": Page „OUT2“ added [T3132]
  • OEM 003/PILLER: "APOJET T II / APOJET LVR": Hide 'Standard' page [T3127]
  • OEM 003/PILLER: "APOJET T II / APOJET LVR": Status Text and Events [T3133]
  • OEM 004/ONLINE: $$PREXTXANTO change on autonomytime and UPS Functions [T3248]
  • OEM 006/EMERSON/VERTIV: 90NET, $$PXSER, Outputvalues to UPS Screen added [T3208]
  • OEM 008/LEGRAND: $$JBUSDAKER: Protokollchanges [T3006]
  • OEM 008/LEGRAND: Daker DK Plus $$JBUSDAKER Screen changes according to LEGRAND insctructions [T3223]
  • OEM 012/GENEREX: UPS ABLEREX $$PRABLER2 UPS screen fix for Output Frequency [T3217]
  • OEM 016/EATON: $$PWXCP Protokollerweiterung [T3094]
  • OEM 016/EATON: $$PWXCP: PW 9170 12.0 Plus communication did not start [T104/#3267]
  • OEM 022/BORRI: Problem with Autonomytime Display at EVO-Protocolls fixed [T2947]
  • OEM 028/AKKUTRONIK: X-Plus TE 10kVA $$MBTAURUS DataLog.csv logging fixed [T3076]
  • OEM 035/WAERTSILA: $$JOVY, $$JOVYIB: UPS internal AlarmLog added [T3295]
  • OEM 036/ABB: $$CONCE: Bugfix Status "Input AUX Bad" if there is no 16,7Hz System detected
  • OEM 036/ABB: CONCE Screen - Modulevalues from Report "ups.modules" compiled [T528/#2713]
  • OEM 044/Henkelhausen: Changed EAST HE-PX 3160 Modular = $$MEGA and EAST HE-PX 3600 Modular = $$MEGA
  • OEM 045/WOEHRLE STS 3000-4000 STSTUMEL added
  • OEM 050/CENTIEL: $$CENTIEL False alarms [T3336]
  • OEM 050/CENTIEL: $$CENTIEL SNMP Protocol, bad input frequency [T3287]
  • OEM 058/SIEL: EMM Multimeter, Adjusting Values in UPS Screen [T3120]
  • OEM 058/SIEL: Solar DSP, $$SIELINVDSP, Screen added [T3197]
  • OEM 058/SIEL: SOLAR Inverter, $$SIELINV, Screen added in CS141 [T3199]
  • OEM 066/AKI: $$SENT2 (SENTRY MS/S): Via SNMP Bypass- and Outputvoltage changed to 0 in random [T3294]
  • OEM 078/SICOTEC: "SLC ADAPT-X 10-90kVA" $$MBSALIRM, Autonomytime did not change, fixed with [T3228]
  • OEM 081/CET: Redundancy lost alarm added to TSI [T188]
  • OEM 082/SALICRUC: $$AEGSER Full Battery Test failure [T3098]
  • OEM 087/ADPOS: Added MID J K RT

1.66 - 180122

22. January 2018

Normal Update

Added Features

  • Added license info on page System > About.
  • Dual Flashrom detection [T3057]
  • Menue changes:
  • Stripped board no. from 'Serial No.' on page System > About.
  • Minor other changes to panels/labels on page System > About.

Changed Functionality

  • Menue changes:
    • Stripped board no. from 'Serial No.' on page System > About.
    • Minor other changes to panels/labels on page System > About.

Bug Fixes

  • Update options 'Reset (network) to factory settings' are inoperable [T3237]
  • Restore of old configurations may later cause Server Error (500) [T3258]
  • Increased delay/timeout for re-login after a firmware update.
  • IE 11 was shown as outdated Browser. ScreenLib "System and Browser Requirements" updated [T3245]
  • Timeserver Settings are not applied [T3253]
  • Pipe-Thru Slave did not show 'Communication Lost' [T3232]
  • BACS Communication lost at less than 3 BACS modules did trigger Thermal Runaway Alarm [T3243]
  • UNMS gets a network lost when the UPS device is deactivated [T128/#3234]
  • Event Job 'UPS Shutdown': Parameter 'Restore Time' now optional [T3224]
  • Buscable disconntected did not trigger BACS Events [T3250]
  • UPS Custom Thresholds Functionality completed [T3061]
  • With IE 11 it is now possible to change COM devices [T3265]
  • BACS ‘Communication Lost’ harmonized with UPS behaviour [T3264]
  • Changes in UPS options caused to delete event list [T3255]
  • Misconfiguration of E-Mail Server causes 'Server Error 500' [T3236]

OEM customer specific features, changes and fixes

  • OEM 003: "APOJET T II / APOJET LVR": Seite „OUT2“ fehlt [T3132]
  • OEM 003: "APOJET T II / APOJET LVR": 'Standard' Seite teilweise ein-/ausblenden [T3127]
  • OEM 003: "APOJET T II / APOJET LVR": Auswertung Eventworte u. Statusanzeige [T3133]
  • OEM 006: 90NET, $$PXSER, Outputvalues to UPS Screen added [T3208]
  • OEM 008: Daker DK Plus, $$JBUSDAKER: Screen changes according to LEGRAND insctructions [T3223]
  • OEM 012: UPS ABLEREX $$PRABLER2 UPS screen fix for Output Frequency [T3217]
  • OEM 016: $$PWXCP Protokollerweiterung [T3094]
  • OEM 022: Problem with Autonomytime Display at EVO-Protocolls fixed [T2947]
  • OEM 036: $$CONCE: Bugfix Status "Input AUX Bad" if there is no 16,7Hz System detected
  • OEM 036: CONCE Screen - Modulevalues from Report "ups.modules" compiled [T528/#2713]
  • OEM 044: Henkelhause changed EAST HE-PX 3160 Modular = $$MEGA and EAST HE-PX 3600 Modular = $$MEGA
  • OEM 045: Woehrle STS 3000-4000 STSTUMEL added
  • OEM 058: Siel EMM Multimeter, Adjusting Values in UPS Screen [T3120]
  • OEM 081: Redundancy lost alarm added to TSI [T188]
  • OEM 082: $$AEGSER: Altervac ZY120-1K Full Battery Test failure [T3098]