Added Features
- #2911: Implementation of CON_AUX4 and it's configuration
- #3045: Backup/Restore function of CS141 fixed with this version
- #3072: Add “Trace” Group to "Tools" Page
- #3050: BACS config options for “List modules stringwise” (NOT FIXED !!)
- #2024: ABLEREX Transferswitch OEM 012, 017, 045: Ablerex STS Transferswitch added
- #2689: During "Initialising" phase the RS232 communication can be monitored via Firefox, Chrome or Safari Webbrowser at URL "http:///trace/ups"
- #3081: CS141 with CONAUX4 or CONRAUX4 or SENSORMANAGER supports now Alarmmanagement with UNMS software
Bug Fixes
- #3083:(and subtickets #3099,#3089)UNMS shows "communication lost" at CS141 alarmstatus. Fixed with this version. (UNMS update required)
- #2864:(and #3118) Timeserver switches back to Greenwich after update, UPS time sync error is suppressed for manually time setting, added Timezones with DST (if available)
- #2964: Issue with passwords containing special characters fixed
- #3120: Missing BACS flag registers in modbus
- #3044: Email Traps transmitted empty subjects
- #2822: UPS Alert History is hidden if UPS does not support this feature
- #2991: Datalogentries -9999, now showing not available DataLog entries as "n/a"
- #3089: UNMS unreachable problem solved with this version
- #2969: BACS Programmer minor fixes
- #3000: Q-Script Error for SNMP_CODE with Pnnnx Variables could cause missing values in SNMP requests for upsBatteryStatus, upsEstimatedMinutesRemaining, upsBatteryTemperature, and other values. Fixed with this version
- #3090: Emailconfiguration was not cleared at a firmware factory reset, fixed with this version
- #3083: False alarms from CS141 at configuration changes fixed
- #2976: CS141 LED activation for device communications lost, red led is shown for missing communication for any connected devices
- #3054: MessageBox after update automatically closes
- #3057: - “Reset to factory” is set when updating other OEM
- #3067: BACS minor differences between CS121 based BACS and CS141 based BACS SNMP Walk eliminated
- #3105: Modbus/IP Slave ID configuration fixed in this version
OEM customer specific features, changes and fixes
- MULTIMATIC ID 17: Added MD-6000T series
- SOCOMEC ID 77: Download for Software enabled
- SICOTEC ID 78: UPS modellist clean up - removed all older UPS models (NOTE: This may cause loosing configurations when updating from older devices to this version)
- GKLEIN ID 62: #3088 Fix for serial communication for $$KLEIN1
- PILLER ID 3: #3030 Batterietemp. fix for UNIBLOCK UBT IV, Missing events for "UNIBLOCK UBT IV",
- #3017: added data at SNMP Walk for UNIBLOCK UBT IV, #3003 change offset to +167
- BENNING ID 19: #2999, added BENMOD Enertronic L 3-3 missing SNMP values, SNMP load zero value for $$PILMOD/$$BENMOD
- LEGRAND ID 8: #3060 KEOR T - Auto Restart removed at Functions Page and changed visibility of output switches for TRIMOD
- EFFEKTA ID 32: #3020 EFFEKTA MKD 1000 RT XL, $$XONL12D, Load > 80/90% logging now fixed
- All OEMs using CENTRALION GRIPOWER: (AEG, Riello Multi Guard GMT and others) #2914, #2933 Logging of faults and warnings
- ADPOS ID 87: #3093 Added "Micro Pro V" with $$WOEHRLE as protocol
- ASTRID ID 38 : EVO Time Sync now OK with this version
- AGIT ID 99: UPS-Alert-History Modifications for $$XONL12B, ETXL modelnames changes
- PIVITOL Power ID 20: 1.5kVA and 3.0 kVA UPS with SALISEC protocol has a new screen
- ABB: Removed unsupported baudrates from setup ABB OEM 036 CONCE protocol