1.38 - 160927

27. September 2016

Normal Update

Added Features

  • First version with support for BACS WEBMANAGER 4
  • SNMP B-2 subtree added

Bug Fixes

  • BACS B4 is now triggering General Alarm in case RI values are out of range of sensors (This was not
    the case in earliere BACS systems, here a "n/a" at RI did not cause a General Alarm. Changed with this
    version.
  • #2972 + #3012 Time sync for all UPS makers protocols aligned to the same code
  • #2426: Datalog and Datalogchart had a wonrg timestamp, fixed now in UTC format. One hour time shift fixed

OEM customer specific features, changes and fixes

  • BORRI/ASTRID: #2972 EVO Type 11 issues with internal clock sync and internal black box fixed
  • PILLER: #3003: UBT IV Messwert Operation Hours
    • #2987: Attaching PILLER Eventrcorder to Emails
    • #3005: added Modbus-Adress 999 for Status "Communication lost"
    • #2985: added webpage for device specific functions
    • #2935: added email transmission through PILLER Gateway
  • LEGRAND: #2963 + #3008 Several fixex for Trimod, including Clock Sync
  • WAERTSILA/JOVYATLAS: #2849 added new UPS protocol for "Waertsila MODBUS" for JOVYCUBE
  • MANNSHARDT: #2787 Enhancements for VOLTRONIC protocol PREXT

1.36 - 160830

30. August 2016

Normal Update

Added Features

  • #2998:Start of SNMP service at system boot
  • Modbus RS-232/RS-485 performance, faster response than previous versions
  • #2966: Modbus communication with multiple masters
  • #2895: Refresh Buttons für EventLog and DataLog and RCCMD Certificates

Bug Fixes

  • #2930: Switch outlet buttons for $$PRABLER2 caused error 420
  • #2990: Network DIP Switch on CS141R_2 hardware
  • #2467: Logging "Log files rotated" only for AlarmLog
  • #2847: SENSORMANAGER fixes for alarm thresholds
  • #2978: Bugfix for FW 1.32 "Memory Leak in AUXDevice::GetData(...)Backend gxserve v0.2.04 at CS141 with sensors connected
  • #2992: Internals logging from SNMPd disabled

OEM customer specific features, changes and fixes

  • AEG: Disabled UPS On/Off functions for $$CBSRn
  • AEG: Limited UPS event history to 50 items for $$CBSRn
  • AEG: #2973: Protect B (AEG, OEM 2), FW 1.32, fehlerhafte Kommunikation
  • PILLER: Modbus Mapping of UPS registers
  • PILLER: Modbus write commands for UPS registers
  • PILLER: Pages/Screens for UPS specific functions
  • PILLER: Acknowledge function for UPS event history items
  • PILLER: UTF-8 encoding of UPS event history
  • PILLER: AR Comfort added UPs Alert history ($$SENTRY and related)
  • PILLER: #2891: IP-switching via PILLER Gateway CS141DMINI
  • PILLER: #2932: internal Pull-Down resistors now configurable per SW
  • PILLER: #2984: Piller (oem3): Illegal Data Address
  • PILLER: #2986: Special characters cause „Parser Error“ in event text
  • PILLER: #2988: Acknowledge of Event text
  • PILLER: #2985: Missing specific "devicefunctions"
  • PILLER: #2989: Write commands Modbus TCP implemented
  • CENTIEL: Implementation of "Centiel UPS"
  • EFFEKTA: Removed UPS models ""EFFEKTA MKD 700 RM RT" up to 3000 RM RT and added "EFFEKTA MKD 1000 RT XL" series up to 3000
  • EFFEKTA: Changed MKD RT series protocol from AETSER to XONL12D
  • EFFEKTA: Logo changed
  • WISAG: Removed as OEM ID 20 and replaced by PIVITOL POWER
  • PIVITOL Power: New OEM ID 20

1.34 - 160810

10. August 2016

Normal Update

Bug Fixes

  • #2734: Logentry removed at false ID requests. Additionally the timeout on the COM1 side at MODBUS protcols has been increased from 4ms now to 50ms.
  • #2966: MODBUS request to false IDs are not longer responded
  • "RS232 Locking" implemented to avoid buffer overflow at RS232 port

OEM customer specific features, changes and fixes

  • CONTROLLED POWER: #2909 various changes on frontend
  • ASTRID/BORRI: #2637 Added Polish language to UPS EVO Screens
  • EFFEKTA: Logo changed
  • EFFEKTA: UPS protocol changed MKD RT series from AETSER to X12ONLD
  • EFFEKTA: #2919 Office Plus series added
  • SICOTEC: At OEM ID 78 Twinys 3/1 Pro series protocol changed from AETSER to XONL12B
  • HENKELHAUSEN: At OEM Id 44 adde HE-PX110 and HE-PX330 with PRFLEX and MEGAE added
  • ALPHA: At OEM ID 58 changed modellname TripowerX33HIMOD TE into TriPowerX33TE (Ablerex TAURUS)
  • AGIT: First Firmware for AGIT Poland OEM ID 99 (former UPS VISION)
  • ADPOS: at OEM Id 87 added Voltronic Galeon and Otima as Micro-SRTV and Mini_JRT V
  • EMERSON/MASTERGUARD: At OEM ID 6 90net series X3 Port added with USSCU4 protocol
  • All customers using Voltronic PREXT protocol: Changed from calculated autonomytime to values transferred by UPS
  • LEGRAND: Bugfix for Autonoymtime and other smaller fixes on Trimod and related UPS