Added Features
- Added new feature in menue "system - general”: At “Device connected to COM2” are now several options available: “none” (Default), “modbus” (Rs232 or RS485 - depends on CS141 model) and “sensor”. At the menu page “devices -sensors - setup - devices connected to COM2” the user many now define which sensortypes are attached.
Bug Fixes
- Fix for AUX Jobs added with any earlier firmware: Fixed with this version, but update option "Reset
to Factory" has to be applied. #2903
- Fix for SNMP Strings, removed invalid characters #2884 and #2866
- Fix for Email Traps: Last email trap after any alarm was delayed, now fixed with this version. #2421 #2901
- Fix for Alarmlogs: Logging added for FUNCTIONS # 2807
- Fix for DHCP : ARP-Broadcast command send at first startup solves this issue #2904
- Fix for UPS modellist upstyp: Invalid file format corrected to UTF-8 which may have caused empty screens #2906
- Fix for FUILLTEST: Cancel Test was not possible, fixed with this version. #2879
- Fix for MODBUS RS232/RS485 was in previous version active only if CS141 was rebooted, fixed with this version #2795
- Fix for "email process error" in UNMS with CS141: At UPS “Communication Lost” the CS141 has send out emails without JSON attachment, this
caused the alarm "email process error". Fixed with this version, but UNMS update required to version from 30th June 2016
- Fix for SENSORMANAGER, SMTCOM and SMTHCOM: NOTE: All users with CON_R_AUX, SMTCOM,. SMTHCOM and SENSORMANAGER are advised to use "Reset to factory settings" when updating their CS141.
- Bugfix for SMTHCOM and SENSORMANAGER at menue "device", fixed with this version
OEM customer specific features, changes and fixes
- COROMATIC and customers using JBUS SOCOMEC protocol: Bugfix for JBUS Modbus address 3000: Powerfail Counter (MODBUS Address 114), Input Bad (MODBUS Address 120),
Battery Bad (MODBUS Address 115) added #2833
- PILLER: Bugfix PILLER Screen for Model "APOJET S II" #2880 and smaller changeon #2786: MODBUS Adresse 3000 Byte reversed
- PILLER: Bugfix PILLER for UPS model “AP Premium”), this device returned 0 values for SNMP, fixed with this version
- PILLER: Special CS121 featujre to WRITE on MODBUS addresses has been added to PILLER CS141 firmware #2674: Modbus Slave Service
- LEGRAND and OEMs using TRIMOD: Added screens for TRIMOD series for UPS Alert History, Event list, UPS Setup #2605, 2602, 2626
- MAKELSAN: Modellist was empty, fixed with this version #2906
- ASTRID/BORRI: Added modbus data 200-598 for OEM ID 70 #2872
- SIEL: Startup CS141 failed at Flexipower $$SIEL because of RCCMD broadcasting, fixed with this version #2886