1.20 - 160613

13. June 2016

Normal Update

Added Features

  • Password Resetfunction implemented #2824 (available on demand)
  • Alarmlog file not automatically archiving if more than 24 hours no alarm #2682
  • Alarmlog file now sorting function implemented to allow easier to search in this file #249
  • Added functions from CS121 to CS141 for Legrand UPS model KEORT #2868

Bug Fixes

  • Error message "Service -1" after firmware update did not allow to login. Ticket #2689, fixed with this version.
  • Bugfix for error message "server error 503" and "server error 500" - after this message the webserver did not allow any changes, a firmware update to this version is required to fix this problem.
  • Bugfix at SNMP requests during coldboot of CS141: This caused a hangup of the CS141, solved with this version.
  • Ticket #2846 fixed, did not allow to choose a UPS model from the drop down list. Fixed with this version
  • Ticket #2797 and #2389 fixes issues with SENSORMANAGER and SMTCOM and CONRAUX4
  • Ticket #2435 fixed, communication issues with SALICRU protocol and SEC protocol
    Ticket #2833 fix for JBUS protocol, added 2 missing modbus addresses (Powerfail counter 11)
  • Ticket #2699 solved with this version. Modbus data was not available if the modbus client requested data with not support values in its range. Fix with this version, CS141 returns now a 0 or -9999 for not available data so that error message “Illegal Data Address” is no longer displayed in Modbus client.
  • Bugfix for Astrid/Borri "Infinity" #2585
  • Bugfix fro Timeserver #2864 (timeserver changes to Greenwich time zone after a while), address 2+3 now fixed with this version
  • Bugfix for Astrid/Borri RCN Screen #2598 and communication issues with UPS Type 5,9,10,11 (#2798)

OEM customer specific features, changes and fixes

  • New customer STACO ENERGEY removes MYERS and takes it place as OEM ID 94
  • Ticket #2828 missing modbus addresses for SALICRU SLC CUBE3 added (Address 151-166)
  • Bugfix for Legrand Trimode #2605 “UPS Alert History”, fixed with this version

1.18 - 160522

22. May 2016

Normal Update

Bug Fixes

  • Several logins after firmware update could cause server error 503. (#2844)
  • 2818 language problem
  • 2846 borri
  • Ticket #2833: $$JBUSP MODBUS Adresse 114/115/120
  • Ticket #2418: Sprachauswahl
  • Ticket #2846: 1.16.22 160517, keine USV Auswahl möglich
  • Ticket #2821: Rückmeldung an Benutzer wenn Konfiguration einen Neustart des Devices erfordert
  • Ticket #2667: Reboot Button
  • Ticket #2811: UPS “Type 5" und UPS "Type 9" Errors

1.16 - 160512

12. May 2016

Normal Update

Added Features

  • SALICRU: UPSVIEW Screen SLC Cube added values for "apparent power", "output current" #2702
  • Alle OEMs using ABLEREX PRABLER: Added Event "Output Short Circuit" #2715
  • LEGRAND: KEORT added to modellist #2705
  • ABB Conce Protocol: Datalog added Outputpower Phase1,2,3 #2771, Added UPS Events History #2718
  • ABB Conce Protocol: Added alarms in UPSVIEW (Output Bad, Output off, UPS Shutdown, Bypass Bad, Charger Failure)#2696
  • KSTAR YDC and MP and UDC series added

Bug Fixes

  • LED Display at CS141 did not show the correct status as described in manuel #2737, fixed
  • SALICRU: Bugfix, communication issues with SALISEC fixed with this version #2744
  • WOEHRLE: TAURUS Modbus communication did not work with CS141 #2692, fixed with this version
  • ASTRID/BORRI and all realted OEMs: several UPS protocols did not work with real UPS (Simulation was OK).
    • Cause was a not MODBUS conform response at the UPS hardware #2610 #2497, #2625, #2789 fixed with this version
  • Backup progess now correct displayed #2640
  • ABB CONCE protocol: Fix for Reboot button (a server error could happen if enduser click several times on reboot #2667 button while CS141 was still in starting process)
  • ABB CONCE protocol false alarm "Charger Fault" with Simulator software #2696 fixed with this version
  • Wake on LAN fixed #2683
    _ GENERAL ELECTRIC: Bugfix UPs communication for VICTRON2 #2756, #2773 fixed with this version
  • CS141 hostname does now accept non numerical/alphabetical characters6 Hostnamen Sonderzeichen 2832
  • ADPOS: Holdtime changed for Micro S Series
  • EFFEKTA/KSTAR: Modell Thor Modular #2818 did show an error message on the UPSVIEW screen, fixed with this version
  • Double MAC addresses: Some CS141 at customers did show identical MAC addresses, fixed with this version
  • CET : Added 1 * SNMP MIB "TSI" for CS141 series, 2nd MIB "AGIL" is in progress and comes with next FW update #2838