2.16 - 230714

14. July 2023

Normal Update

Added Features

  • Reimplement and improve firmware update check [T4300]
  • BACS: Introduction of a new impedance error ""Blown RI Fuse" [T4028]
  • BACS: Display of Average Resistance Value [T4765]
  • MIB Extension for UPS's with pos. & neg. Battvolt/Battcurrent [T4982]

Changed Functionality

  • SM_T_COM/SM_T_H_COM Visualization improvement [T4979]
  • Some SNMP traps contain more objects than defined in the MIB [T5008]
  • BACS: Setup Screen: Allow only integers when entering "Nominal Capacity per Battery [T4668]
  • BACS: Apply delay of "Discharge Volt Alarm" to "Max. Voltage Difference" as well [T3530]

Bug Fixes

  • RCE vulnerability in NTP configuration [T4989]
  • SNMP service is partially active after factory reset [T4995]
  • UPS RS232 communication does not start when a load higher than the power has been configured [T5006]
  • SiteManager 6: Archived log files are listed with date 1970 [T4970]
  • Wrong warning about "Gateway is in other subnet" may appear [T4911]
  • Integration of RS485 Modbus fix for CS141LM HW 161 [T4998]
  • BACS: SNMP resistance query is not answered before first measurement [T3859]
  • BACS: Indicate that the RI measuring value is outside the module measuring range [T3695]
  • BACS: No audible browser confirmation at last programmed module [T4766]

OEM customer specific features, changes and fixes

  • OEM 004: $$PREXTXANTO, $$PREXTZINTO, difference between UPS screen values and SNMP values [T4967]
  • OEM 004: $$PREXTZINTO (ZINTO 1000 (Mod.2017)): Charger failure will not be recognized [T4997]
  • OEM 008: KEOR MOD, $$KEORMOD, SNMP upsOutputPower values are wrong [T4964]
  • OEM 008: $$KEORMOD (KEOR MOD): Add event "External Battery Switch open" [T4965]
  • OEM 008: Added "KEOR XPE" modular UPS
  • OEM 012: Added "KEHUA MR33" modular UPS series
  • OEM 015: Renamed PowerValue G2 series
  • OEM 017: Missing Modbus value at MD-1000PRO Slot [T4952]
  • OEM 017: New Protocol for ML RT 750 GEN ID 436 [T4980]
  • OEM 022: $$MBTAURUS: System Screen Temperature Values "0.00°C" [T4895]
  • OEM 025: Changed "Rubin Plus 6-10 kW" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 028: $$GPSER (X-Plus MST 40): Scheduler battery test is no longer working [T4974]
  • OEM 028: Changed "Continuity Plus 6kvA/10kVa" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 029: Renamed PowerValue G2 series
  • OEM 035: Added "JOVYSKY Q" UPS
  • OEM 036: $$XONL12C: (Power Value 1/1 (R)(T)1-10kVA): Scheduler battery test is no longer working [T4983]
  • OEM 036: Renamed PowerValue G2 series
  • OEM 045: Renamed UPS series "Convert II" to "CON2"
  • OEM 045: Added "KEHUA MR33" modular UPS series
  • OEM 047: Changed "DK Plus 6kVA/10kVA" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 050: $$CENTIEL2: Scheduled battery test fails with invalid argument [T4450]
  • OEM 050: $$PRABLER(3): Wrong UPS Autonomy Time [T4408]
  • OEM 057: Added "PowerTower Green" modular UPS
  • OEM 059: Changed "Continuity Plus 6kvA/10kVa" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 061: Added "Matrix 1-3kVA" and "HUAWEI E/G/A" UPS series
  • OEM 062: Changed "Minicompact 2 6kW/10kw" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 066: Added "Ultron DPS Gen.2" series, "Ultron HPH Gen.2" series and "Modulon DPH" series
  • OEM 078: Integration of Matrix MXT/MXRT UPS series [T4988]
  • OEM 084: Updated their OEM Logo
  • OEM 087: Added UPS "Midi 10-100 series", "Midi J S series", "Maxi 10 - 800 series" and "Maxi J S series"

2.14 - 230329

29. March 2023

Normal Update

Added Features

  • BACS: Add Discharge Counter Reset option [T3470]
  • Implement encryption for the UPSTCP protocol [T4863]
  • Show warning message when default password is used [T4887]
  • Enable configuration of multiple email trap recipients [T4880]
  • Display the #LOCATION variable in a more prominent position [T4853]

Changed Functionality

  • Turn on TLS for RCCMD & UNMS services by default [T4955]
  • Display the contents of the Datalog as a table view [T4303]
  • Megatec 3-phase series:, $$MEGA, $$MEGAE CS141 UPS screens improvement [T4875]
  • BACS: After discharging, keep the higher log rate for a short time [T2866]

Bug Fixes

  • Wrong Analog Sensor Events at SITEMANAGER 6 [T4630]
  • "Forgot password" reset procedure no longer works [T4933]
  • With series SCM on hw161 the RS485 interface does not work [T4969]
  • Unsupported Modbus addresses that have a factor defined will be displayed [T4922]
  • Local admin can not log in if option "Radius, than local" is enabled without RADIUS server [T4862]
  • $$MEGA(E) (Megatec 3-phase): Display of Ext. information values overlap the input icon [T4875]
  • New Netfinder available for searching CS141 with SSL/TLS encryption in networks - available from GENEREX website as free download
  • ALL OEMs using APC SNMP network cards Type 2 and MGE Galaxy 300 with UNMS : New UNMS fixed communication issues [T4949]

OEM customer specific features, changes and fixes

  • OEM 003: Apotrans III: Replace "UPS" with "STS" in the "UPS Event History" menu item [T4873]
  • OEM 004: $$PREXTXANTO: ComLost/Restored several times per day [T4884]
  • OEM 004: UPS function "Battery deep discharge protection" does not work [T4957]
  • OEM 008: $$KEORMOD (KEOR MOD): Add event "External Battery Switch open" [T4965]
  • OEM 011: New OEM Partner SANDERElektrische Anlagen - first version - supporting all standard UPS from OEM ID 12
  • OEM 022: BORRI Legrand changed SNMP traps for EVO series of battery bad A1,A6,A9,A10,A16,A20,A23,A24,A51 from red (Alarm) to blue (Informational)
  • OEM 035: $$EVO2 (JOVYSTAR-PLUS-E): Various measured values require corrections [T4846]
  • OEM 035: JOVYATLAS typo in UPS modellist JOVYTEC L series corrected
  • OEM 038: ASTRID changed SNMP traps for EVO series of battery bad A1,A6,A9,A10,A16,A20,A23,A24,A51 from red (Alarm) to blue (Informational)
  • OEM 039: KAMIC Sweden has changed their Logo
  • OEM 045: MGESHUT3 (Windstar UPS): UPS custom thresholds no longer at present [T4973]
  • OEM 047: S2S Legrand changed the protocol for KEOR HPE to "EVO5"
  • OEM 050: Add SNMP variable for Output Energy Consumption [T4897]
  • OEM 050: $$CENTIEL2 (Centiel UPS (since 2020)): Add Input Current Values [T4919]
  • OEM 050: $$CENTIEL/$$CENTIEL2 Removed UPS Control Function [T4920]
  • OEM 055: Integration of "Kehua MYSerie" UPS protocol [T4929]
  • OEM 055: COROMOATC added "DELPHYS GP 2.0 Touch 160-800kVA"
  • OEM 056: PTI Predictive Technology USA received new FAVICON
  • OEM 065: ELINEX has changed their Logo
  • OEM 070: ASTRID NEUTRAL changed SNMP traps for EVO series "Device Type 1" battery bad A1,A6,A9,A10,A16,A20,A23,A24,A51 from red (Alarm) to blue (Informational)
  • OEM 071: Implementation Voltronic Arena UPS [T4915]
  • OEM 071: INFOSEC France added "Mod3" with Voltzronic protocol PREXTMULTI
  • OEM 077: $$XONL12 (Power Value 1/1 (R)(T) 1-10kVA): Show temperature on UPS screen [T4947]
  • OEM 077: $$XONL12C (Power Value 1/1 (R)(T) 1-10kVA): Wrong statuses are displayed during the battery test [T4958]
  • OEM 082: $$MBADAPT2 (SLC ADAPT2): Use ADAPT-X modbus mapping [T4805]
  • OEM 087: $$MBSALIRM2 "HiUp series" Event & Screen Extension [T4903]
  • OEM 087: $$MDELTA: Wrong calculation of autonomy time when UPS does not support it [T4948]

2.12 - 221214

14. December 2022

Security Update

After upgrading to this firmware version, it is no longer possible to downgrade to a lower version.

Added Features

  • Include OEM specific favicon's [T4364]
  • Include OEM specific page title [T4580]
  • Display a warning if the system time is invalid [T4784]
  • Show warning message when default password is used [T4887]
  • Implement feature to send commands to another CS141 [T401]
  • eMailTrap Heartbeat: Add some device info to default subject line [T4114]

Changed Functionality

  • Always use HTTPS by default [T4890]
  • Turn off non-mandatory connectivity services by default [T4881]
  • Reduced power consumption for hw161 based slot cards [T4889]
  • BACS: Increased the number of configurable GX_R_AUX [T4833]
  • $$MBTAURUS (Taurus Modbus): UPS screen improvements [T4840]
  • BACS: New battery capacity calculation for batteries in "idle" state [T4812]
  • Implemented 'BUDGET LC' series features lock / unlock via license [T3195]
  • BACS: Supply the current sensor values via Modbus and SNMP with decimal places [T4839]

Bug Fixes

  • Restrict uploads to specific file types [T4899]
  • Verify authenticity of the update package [T3168]
  • Verify files types within the backup archives [T4894]
  • GX_R_AUX Status LED remains green at ComLost [T3660]
  • Archived log files are listed in web interface with invalid date [T3281]
  • Missing configuration for UPS battery too old at SNMP protocol [T4817]
  • Deactivated local users are deactivated only after the first WebApp login [T4885]
  • The UPS Event Job "UPS Offline" does not switch the UPS into bypass mode [T4810]
  • Multiple expanded events can lead to the last entries not being visible anymore [T4052]

OEM customer specific features, changes and fixes

  • OEM 002: AEG added PROTECT 1 (LCD) with XONL12B2
  • OEM 002: $$AETSER (Protect 1.100bl + 1xBP20): Some UPS functions are missing [T4801]
  • OEM 003: $$PILMOD10 (UNIBLOCK UBT IV): The screen is missing lines in front of the inverters [T4859]
  • OEM 008: LEGRAND TRIMOD BACnet section changed
  • OEM 008: $$TRIMOD ("Trimod"): 3-phase UPS shows incorrect frequency values [T4844]
  • OEM 008: $$TRIMOD (Trimod): Charging voltage and current are displayed wrong [T4842]
  • OEM 008: $$ECONT (WHAD HE 800/1000/1500): Read out battery values from UPS [T4883]
  • OEM 012: GENEREX NEUTRAL Added Smart offline UPs 12V-488V
  • OEM 012: GENEREX NEUTRAL added DELTA SNMP Card support for OID .1.3.6.1.4.1.2254.2.5.7.x DELTA MIB (UPSv5.mib)
  • OEM 012: GENEREX NEUTRAL added INVT HT33 Series
  • OEM 015: Newave Name change to ABB CH
  • OEM 017: MULTIMATIC: MD-PRO Slot UPS received a fix for UPS firmware back in FW 2.10 using KSTAR2 protocol (MD, MDO Series)
  • OEM 020: $$SALISEC ("Trusted/Tactical UPS"): Display "NA" for Battery when UPS is not in Backup [T4845]
  • OEM 022: BORRI added to "UPS Type 12" (and all other UPS using that protocol) new SNMP Traps
  • OEM 022: $$MBTAURUS System Screen Temperature Values "0.00°C" [T4895]
  • OEM 028: AKKUTRONIK Continuity Default Holdtime changed to 4 Minutes at 100% Load
  • OEM 029: Newave Germany name change to ABB DE
  • OEM 029: JOVYATLAS received new Logo
  • OEM 032: EFFEKTA Transferswitch ATS 16 received new EVENT and SNMP section $$ATS16 SNMP_STS MOD_ATS16
  • OEM 036: $$CONCE ('Upscale') scheduled battery test delivers wrong test result [T4850]
  • OEM 044: ABLEREX received new UPS model Modular UPS MD, TS, KR, MSII, MS, AR, OD, TT, TT GT, ATS
  • OEM 044: ABLEREX logo removed
  • OEM 050: $$CENTIEL(2): UPS Alert History: The order of the events is not correct [T4324]
  • OEM 050: Add Modbus register for "Output Energy Consumption" [T4856]
  • OEM 060: DFM SELECT extended SENTRYUM Events by Bypass bad/OK
  • OEM 064: LEISTUNG BRAZIL added Multi Sentry MST Series
  • OEM 064: LEISTUNG BRAZIL added NextEnergy NXE Series
  • OEM 065: ELINEX added Elinex IG200 Mod. 2022 Generator
  • OEM 070: ASTRID NEUTRAL changed EVO 5 SNMP Alarmtraps battery bad, A1, A6, A9, A10, A16, A20, A23, A24, A51 from red (Alarm) to blue (Informational)
  • OEM 072: ETEC added E-Tec Sentinel, Sentryum, Mult Power series
  • OEM 077: $$XONL12C (Power Value 1/1 (R)(T) 1-10kVA: A manual switch-off of the UPS is not recognized [T4800]
  • OEM 078: SICOTEC added MACAN series and EA 900 Pro RT
  • OEM 078: SICOTEC added EAST-LION series
  • OEM 079: ELTEK becomes DELTA and added support for DELTA SNMP Card support for OID .1.3.6.1.4.1.2254.2.5.7.x DELTA MIB (UPSv5.mib)
  • OEM 080: POWERSHIELD Australia first OEM release version with Arena, Platinum, Centurion, Commander, Defender, SafeGuard, Gladiator Series
  • OEM 082: SALICRU SPAIN added SLC Twin RT 3/PRO3
  • OEM 082: SALIRCU added SLC TWIN PRO3, RT3 with 3 and 4 KVA using new modbus protocol MBINNOVA
  • OEM 082: SLC ADAPT2, $$MBADAPT2, problems with the display of the frequencies [T4799]
  • OEM 082: Integration of the "TWIN PRO3/RT3" UPS and protocol [T4814]
  • OEM 087: ADPOS added Mini J II Series,
  • All OEMs using RIELLO SENTRYUM UPS: Changed Event section from "EV_AE" to "EV_GPSER" and added new SENTRYUM Events by Bypass bad/OK
  • All OEMs using Automatic Transferswitches ATS/STS: Introduced new EVENT section, new Modbus section, new SNMP section