After upgrading to this firmware version, it is no longer possible to downgrade to a lower version.
Added Features
- Major firmware system update for increased security and reliability [T3108]
- Email-Traps support added for SiteMonitor
- BACS: SNMP Values for bacsAvModuleVolt and bacsTotalVolt [T3906]
- RCCMD client passwort restrictions improved (5 characters minimum)
Changed Functionality
- BACS improved 'Discharge detection source = Automatic' [T3784]
- BACS accelerate measurement interval for impedance (RI) [T3896]
- BACS current sensors CSH400/2000 measurement accuracy increased [T2993]
- UNMMS protocol "RFC 1628 SNMP" alarm detection now less strict implemented to avoid issues with 3rd party SNMP cards not sending the correct number of SNMP alarms at upsAlarmsPresent.0 (HUWAEI and EATON cards)
Bug Fixes
- BACS: C40 modules will longer not generate 'impedance high' alarm if value is out of range [T3734, T2907]
- Configuration issues for SITEMANAGER and SITEMONITOR at COM2 fixed [T3879]
- SITEMANAGER 6 added SM_II_DIG sensor [T3876]
- Custom Threshold "UPS Temperature High Alarm off" job fixed [T3799]
- Email Bulk edit beyond 60 jobs per event caused "Server Error (413). Error message now "Too many jobs" [T3883]
- UNMS added E-Mail Traps for SENSORMANAGER and added UPS/CS141 link button and the names for digital IO's
- Fixed internal reset to UTC timezone during update [T3911]
- SITEMANAGER/SITEMONITOR 6 configuration COM 2/3 [T3918]
OEM customer specific features, changes and fixes
- OEM 002: AEG new Protect C (LCD) implemented [T3658]
- OEM 002: AEG first version of "CS141BSC/L as "LC" (Low Cost" series with limited UPS support up to 6KVA
- OEM 003: PILLER Function Screen Changes [T3887]
- OEM 003: GXSERVE Daemon memory leak problem solved by OutOfMemory-Guard service [T3605]
- OEM 003: At "AP PREMIUM" the name "UPS" changed to "Converter" [T3909]
- OEM 004: ONLINE Xanto 2017, $$PREXTXANTO, Changes on UPS Functions [T3924]
- OEM 008: LEGRAND implementation KEOR PDU 800 [T3881] and UPS model list sorted aphabetically
- OEM 008: LEGRAND implemented new KEOR MOD UPS seriesl [T3650]
- OEM 017: MULTIMATIC UPS model list sorted
- OEM 017: MULTIMATIC added UPS model series "ML-T" with $$PREXT (Problem T3916 wrong display of load was still present at this time)
- OEM 017: MULTIMATIC changed SOCOMEC protocol JBUS protocol at "Commlost" detection because of unstable versions found in the field [T3890]
- OEM 021: EREPI OP 3000 RT changed battery voltage calculation
- OEM 025: ROTON added Gustav Klein UPS series
- OEM 032: EFFEKTA added UPS model UDC One 6kVA - UDC One 10kVA
- OEM 032: EFFEKTA added UPS model series "RT-Industrie"
- OEM 032: EFFEKTA changed "EFFEKTA OFFICE" series to protocol $$PREPC (after switching to $$APEX)
- OEM 032: EFFEKTA changed "EFFEKTA OFFICE HOME 800" to protocol $$PREPC
- OEM 036: ABB protocol $$XONL12C Monitoring Screen wrong data display fixed [T3762]
- OEM 050: CENTIEL: Fix for modular installations with more than 9 modules [T3919]
- OEM 051: MITSUBISHI Introduce Mitsubishi's logo and red color in webApp [T3895]
- OEM 051: Mitsubishi Model 9900D [T3838], Model 9900 AEGIS [T3831], Model 1100B [T3833], Model 1100A [T3832]
- OEM 051: Mitsubishi Model 9900B [T3834], Model Summit [T3835], Model 9900C [T3836], Mitsubishi Model 9900CX [T3837]
- OEM 055: COROMATIC changed SOCOMEC protocol JBUS protocol at "Commlost" detection because of unstable versions found in the field [T3890]
- OEM 058: SIEL added 'Input Auxiliary' status bits to all SIEL_TRAPMSG [T3711]
- OEM 060: DFM SELECT added SALICRU SLC TWIN PRO2, RT2, SLC CUBE3+, SLC X-PERT, SLC ADAPT X, SLC ADAPT series
- OEM 062: GUSTAV KLEIN added ROTON UPS Rubin as "Minicompact 2" series
- OEM 082: SALICRU added ASTRID SCL-80-XPERT B1 series
- OEM 084: UPS Ltd./ KOHLER Group added PW9250 DPA-250 50kVA and PW9250 DPA-300 50kVA