1.56 - 170512

12. May 2017

Normal Update

Added Features

  • New default at BACS: #3379 - to improve the scanrates at a discharge, a new configuration option is availalbe "Optimized Scan". (Default ON).
    • This function does improve the voltage updates during a discharge.
  • T79 (#3306): Introduced workaround for false Red LED on BACS modules: Those BACS modules show a red LED although no alarm is present.
    • It is caused be external noise issues and affected is only ID 1 and ID 257. Workaround: During RI measuring the thresholds of ID 1 and ID 257 are checked if there is any threshold lower than 0.01, if this is the case, BACS WEBMANAGER is resetting the threshold to 0.01 and resets the alarmbit, which turns the LED green again.
  • T2907: At BACS C40 modules measuring batteries with less than 0.02 mOhm will now appear a new information on the BACS screen that the actual values are < 0.02mOhm (before: N/A)
  • T2862: Free configurable BACS temperature thresholds added
  • T506: CS141 BUZZER as AUX-Device implemented [#2747]
  • T157: Translations added [#3199]

Changed Functionality

  • T57: DataLog Chart timeline improvement [#3342]
  • T2875: About-Page added more informations

Bug Fixes

  • T2913: Fix for BUZZER Event Configuration Server Error (400)
  • 3400: UPS Alert history through Email fixed

  • T2859: Before changing a ups model, the CS141 does now allow to save the previous configuration
  • T2877: Change form C° to F° will now also adjust the Thresholds
  • T1974: RCCMD is missing the up/downn button, Rccmd redundancy configuration and test button was missing
  • T2910: Fix for SENSORMANAGER, apply button activated
  • Com 1 noise issue: T308 - If a UPs trasnmitts noise over the RS232 cable to the COM1 of the CS141,
    it could happen that the device does not start. (No webserver). If the noise level is not removed (by
    isolating the RS232 cable), than the enduser would not see that the noise is the cause of the issue
    and the problem is related to the CS141 - which is wrong. In this firmware we introduce a noise filter
    on COM1, in case noise causes a crippled RS232 communication, the CS141 does now now start up and the
    webinterface will be available, but it still does not guarantee that the CS141 can communicate with the
    noise emitting UPS. But this firmware changes makes it obvious for the enduser that the UPS is the cause
    of the problem, not the CS141

OEM customer specific features, changes and fixes

  • COROMATIC: Changed baudrate of "ITYS2 1000-100000VA UPS 230V" from 9600 to 2400 baud
  • SALICRU: T81: $$MBSALIRM, added internal Modbus values [#3304]
  • WOEHRLE: added CONVERT 1000-3000S2 and WISUS WP (CENTIEL)
  • SAPOTEC: removed "Sapotec Serie ZP-20K"
  • EFFEKTA: change at ADIRA (XONL12C)
  • ONLINE: added ZINOT 2017 and XANTO 2017 series with new PREXT protocol
  • LEGRAND: T2880 ($$ECONT2) Megaline Screen values corrected
  • PILLER: T9: AP Premium Adapter-Events [#3403]
  • CENTIEL: T2881 added Modbus section, T16 $$Centiel: Ups Alarm History Text updated [#3393]
  • POWERNET Finnland: T61 - further changes on Powernet DAC screen (#3388)
  • CET: T2890 - CET TSI Screen changes
  • all customers using TOSHIBA protocol SEC 9600: T2891 - Fix for upsInputTruePower at SNMP

1.54 - 170405

5. April 2017

Normal Update

Added Features

  • Timeserver tests are now returning a result in the CS141 logfile
  • First version supporting CS141 BUZZER as AUX device T506/#2747

Changed Functionality

  • Text adjustments in german language mode T157/#3199 and french T41/#3363

Bug Fixes

  • "Optimized Scan" button fixed T29/#3379
  • Shutdown RCCMD signal changed for AS400/iSeries compliance, fixed with this version #3385
  • Fahrenheit / Celsius configuration fixed on all UPs screens T405/#2890
  • Webserver frontend timeout increased to avoid error messages "<503> backend busy”
  • Bugfix on BACS Programmer Webpage in CS141/B4 T2865

OEM customer specific features, changes and fixes

  • AEG: Modelname Protect Plus M600 changed, interal Modbus registers now transferred to Modbus over IP #3304
  • ADPOS: Energycounter added to Sensormanager T114/#3253
  • ABB all : Emailtrap configuration changed to notify the user about missing input T13/#3397,
    $$CONCE, Timeserver - UPS Time Synchronisation did not work correct, fixed with this version T1/#3412
  • ABB ID36: SSB project - #3407 - Protocol CONCE, backend hangup fixed when only 1 input line found (upsdev v1078,
    Emailtrap configuration changed to notify the user about missing input T13/#3397
    $$CONCE, Timeserver - UPS Time Synchronisation did not work correct, fixed with this version T1/#3412
    $$CONCE: System measures of disappeared module still visible T18/#3391
  • BORRI/ASTRID: Change log entry at $$EVO2 + $$EVO3 - if ups communication was lost, the log entry if the job "Event System Shutdown2 is logged T1082/#1895
  • EFFEKTA: Changed protocol of EFFEKTA Adira 1/1 6kVA" to $$XONL12C (before CONQ) and EFFEKTA Adira 1/1 10kVA" = $$XONL12C
  • KESS: Changes on BatteryX implementation T256/#3086
  • ONLINE: First firmware supporting new ZINTO 2017 and XANTO 2017 T67/#3022
  • LEGRAND: First version of integration Ablerex DK Plus UPS with JBUSMODULYS protocol #3290 (not finished)
    TRIMOD, TRIMODHE: Fix at SNMP value upsEstimatedMinutes remaining T2861
  • PILLER: Attach UPS alarmlog to Emailjobs added T269/#3066, APOTRANS III Display corrected T46/#3357,
    AP Premium Adapter-Events added T9/#3403
  • CENTIEL: UPS Events (History) display [ID: 11] [T151/#3205] changed, sN display corrected [T153/#3203] and T151/#3205
  • S2S: Added all LEGRAND UPS models
  • DFM Select and all customers using UPS standard screens: Screen change - added 2nd input line #3402
  • all customers using SALISEC protocols (ID 1 and 12): Modbus values extended
  • GRUENCO: Batteryvoltage value for MARS RT 2000 adjusted
  • CONTROLLED POWER: Load display changed at "UltraLITE (240 or 208V in-out)"$$CPUSA T2850

1.52 - 170307

7. March 2017

Normal Update

Added Features

  • Introduction of "Optimized Scan" - this is a fast discharge mode for BACS.
    • Default is now that during a discharge the only the voltages are measured as fast as possible. This mode does no longer measure impedances, temperatures, current is updated in longer intervals than before. BACS VIEWER is now able to show an improved discharge curve. #3379
  • All customers using standard UPS screens: New screen with extra bypass introduced
  • All customers : Added simple UPS monitor screen [#3322]
  • Added AUX event jobs for switching UPS outlets #3373
  • Limit Thermal Runaway Parameter 'TempDiff' added #3278

Changed Functionality

  • Log messages for switching AUX ports improved #3384

Bug Fixes

  • Bugfix for SENSORMANAGER - switching AUX and SENSORMANAGER OUTPUTs did not work, fixed with this versione #3384
  • Some UPS models "Restore configuration" cause a reset to default event jobs, fixed with this version #3383
  • Deactivation of "Automatic Logout" fixed #3381
  • UPSTCP server hangup while rest of system is still running, fixed with this version #3346
  • BACS current sensor displaye "n.a." at discharge between 0-1A (discharge) solved #3317 & #1015

OEM customer specific features, changes and fixes

  • AEG: Protect M600 screenchanges #3360
  • ABB all : Underline AUX module number on monitor screen added #3391
    • Screen shows -9999V on line1 if no any module found on this line, solved #3392
  • ABB ID36: OEM pre-configuration of Email-traps after firmware-update added #3345
    • Module 3 shows measures of non-present module 2 fixed #3388
    • Mains failure on Line 1 doesn't show frequency as zero, fixed #3389 & #3233
    • Frequency interval improved and display at powerfail changed, module lost display changed #3233
  • ERREPI and all other customers using POWERCOM UPS: Fix for BNTUSB function outlet switching #3372, #3371
  • UPS SERVIS: ABLEREX STS wrong log messages fixed #2024
  • WOEHRLE: ABLEREX STS wrong log messages fixed #2024
  • MULTIMATIC: ABLEREX STS wrong log messages fixed #2024
  • KAUFEL: Logo updated #2389
  • COROMATIC and all SOCOMEC users OEM IDs 17,26,28,47,55,66,67,78,96,100: Added ITYS PRO model and
    fix #3254 (Battery failure and General alarm)
  • KESS: Logo updated
  • ONLINE: Added new UPS models 2017 #3022
  • ONLINE: Change at XANTO S screen #2192
  • LEGRAND: Problem with Battery too old message, was executed after 5 month fixed for TRIMOD protocols #3375
  • LEGRAND: SNMP section ECONT changed, added SNMP values for InputTruePower and OutputCurrent #3367
  • ETEC: Added EC series
  • PILLER: Apostar AS 4 in UNMS unreachable, fixed with this version #3364 (Note: latest UNMS software required)
  • PILLER: Monitor screen for "APOTRANS III" #3357
  • CENTIEL: Improved UPS alarm history display speed after boot #3205
  • CET: Missing SNMP traps for $$CET #3161
  • all customers using TOSHIBA SEC 9600b : various alarm issues fixed at $$TOSHIBASEC #3380.
  • all customers using MITSUBISHI 9xx, 2033, 9800 - protocol $$SALISEC replaced by $$TOSHIBASEC