Added Features
- New default at BACS: #3379 - to improve the scanrates at a discharge, a new configuration option is availalbe "Optimized Scan". (Default ON).
- This function does improve the voltage updates during a discharge.
- T79 (#3306): Introduced workaround for false Red LED on BACS modules: Those BACS modules show a red LED although no alarm is present.
- It is caused be external noise issues and affected is only ID 1 and ID 257. Workaround: During RI measuring the thresholds of ID 1 and ID 257 are checked if there is any threshold lower than 0.01, if this is the case, BACS WEBMANAGER is resetting the threshold to 0.01 and resets the alarmbit, which turns the LED green again.
- T2907: At BACS C40 modules measuring batteries with less than 0.02 mOhm will now appear a new information on the BACS screen that the actual values are < 0.02mOhm (before: N/A)
- T2862: Free configurable BACS temperature thresholds added
- T506: CS141 BUZZER as AUX-Device implemented [#2747]
- T157: Translations added [#3199]
Changed Functionality
- T57: DataLog Chart timeline improvement [#3342]
- T2875: About-Page added more informations
Bug Fixes
- T2913: Fix for BUZZER Event Configuration Server Error (400)
-
3400: UPS Alert history through Email fixed
- T2859: Before changing a ups model, the CS141 does now allow to save the previous configuration
- T2877: Change form C° to F° will now also adjust the Thresholds
- T1974: RCCMD is missing the up/downn button, Rccmd redundancy configuration and test button was missing
- T2910: Fix for SENSORMANAGER, apply button activated
- Com 1 noise issue: T308 - If a UPs trasnmitts noise over the RS232 cable to the COM1 of the CS141,
it could happen that the device does not start. (No webserver). If the noise level is not removed (by
isolating the RS232 cable), than the enduser would not see that the noise is the cause of the issue
and the problem is related to the CS141 - which is wrong. In this firmware we introduce a noise filter
on COM1, in case noise causes a crippled RS232 communication, the CS141 does now now start up and the
webinterface will be available, but it still does not guarantee that the CS141 can communicate with the
noise emitting UPS. But this firmware changes makes it obvious for the enduser that the UPS is the cause
of the problem, not the CS141
OEM customer specific features, changes and fixes
- COROMATIC: Changed baudrate of "ITYS2 1000-100000VA UPS 230V" from 9600 to 2400 baud
- SALICRU: T81: $$MBSALIRM, added internal Modbus values [#3304]
- WOEHRLE: added CONVERT 1000-3000S2 and WISUS WP (CENTIEL)
- SAPOTEC: removed "Sapotec Serie ZP-20K"
- EFFEKTA: change at ADIRA (XONL12C)
- ONLINE: added ZINOT 2017 and XANTO 2017 series with new PREXT protocol
- LEGRAND: T2880 ($$ECONT2) Megaline Screen values corrected
- PILLER: T9: AP Premium Adapter-Events [#3403]
- CENTIEL: T2881 added Modbus section, T16 $$Centiel: Ups Alarm History Text updated [#3393]
- POWERNET Finnland: T61 - further changes on Powernet DAC screen (#3388)
- CET: T2890 - CET TSI Screen changes
- all customers using TOSHIBA protocol SEC 9600: T2891 - Fix for upsInputTruePower at SNMP