1.24 - 160630

30. June 2016

Normal Update

Added Features

  • Added new feature in menue "system - general”: At “Device connected to COM2” are now several options available: “none” (Default), “modbus” (Rs232 or RS485 - depends on CS141 model) and “sensor”. At the menu page “devices -sensors - setup - devices connected to COM2” the user many now define which sensortypes are attached.

Bug Fixes

  • Fix for AUX Jobs added with any earlier firmware: Fixed with this version, but update option "Reset
    to Factory" has to be applied. #2903
  • Fix for SNMP Strings, removed invalid characters #2884 and #2866
  • Fix for Email Traps: Last email trap after any alarm was delayed, now fixed with this version. #2421 #2901
  • Fix for Alarmlogs: Logging added for FUNCTIONS # 2807
  • Fix for DHCP : ARP-Broadcast command send at first startup solves this issue #2904
  • Fix for UPS modellist upstyp: Invalid file format corrected to UTF-8 which may have caused empty screens #2906
  • Fix for FUILLTEST: Cancel Test was not possible, fixed with this version. #2879
  • Fix for MODBUS RS232/RS485 was in previous version active only if CS141 was rebooted, fixed with this version #2795
  • Fix for "email process error" in UNMS with CS141: At UPS “Communication Lost” the CS141 has send out emails without JSON attachment, this
    caused the alarm "email process error". Fixed with this version, but UNMS update required to version from 30th June 2016
  • Fix for SENSORMANAGER, SMTCOM and SMTHCOM: NOTE: All users with CON_R_AUX, SMTCOM,. SMTHCOM and SENSORMANAGER are advised to use "Reset to factory settings" when updating their CS141.
  • Bugfix for SMTHCOM and SENSORMANAGER at menue "device", fixed with this version

OEM customer specific features, changes and fixes

  • COROMATIC and customers using JBUS SOCOMEC protocol: Bugfix for JBUS Modbus address 3000: Powerfail Counter (MODBUS Address 114), Input Bad (MODBUS Address 120),
    Battery Bad (MODBUS Address 115) added #2833
  • PILLER: Bugfix PILLER Screen for Model "APOJET S II" #2880 and smaller changeon #2786: MODBUS Adresse 3000 Byte reversed
  • PILLER: Bugfix PILLER for UPS model “AP Premium”), this device returned 0 values for SNMP, fixed with this version
  • PILLER: Special CS121 featujre to WRITE on MODBUS addresses has been added to PILLER CS141 firmware #2674: Modbus Slave Service
  • LEGRAND and OEMs using TRIMOD: Added screens for TRIMOD series for UPS Alert History, Event list, UPS Setup #2605, 2602, 2626
  • MAKELSAN: Modellist was empty, fixed with this version #2906
  • ASTRID/BORRI: Added modbus data 200-598 for OEM ID 70 #2872
  • SIEL: Startup CS141 failed at Flexipower $$SIEL because of RCCMD broadcasting, fixed with this version #2886

1.22 - 160616

16. June 2016

Normal Update

Added Features

  • Added Modbus over RS485 for CS141SCM and CS141LM

OEM customer specific features, changes and fixes

  • Bugfix for PILLER Modbus address 3000

1.20 - 160613

13. June 2016

Normal Update

Added Features

  • Password Resetfunction implemented #2824 (available on demand)
  • Alarmlog file not automatically archiving if more than 24 hours no alarm #2682
  • Alarmlog file now sorting function implemented to allow easier to search in this file #249
  • Added functions from CS121 to CS141 for Legrand UPS model KEORT #2868

Bug Fixes

  • Error message "Service -1" after firmware update did not allow to login. Ticket #2689, fixed with this version.
  • Bugfix for error message "server error 503" and "server error 500" - after this message the webserver did not allow any changes, a firmware update to this version is required to fix this problem.
  • Bugfix at SNMP requests during coldboot of CS141: This caused a hangup of the CS141, solved with this version.
  • Ticket #2846 fixed, did not allow to choose a UPS model from the drop down list. Fixed with this version
  • Ticket #2797 and #2389 fixes issues with SENSORMANAGER and SMTCOM and CONRAUX4
  • Ticket #2435 fixed, communication issues with SALICRU protocol and SEC protocol
    Ticket #2833 fix for JBUS protocol, added 2 missing modbus addresses (Powerfail counter 11)
  • Ticket #2699 solved with this version. Modbus data was not available if the modbus client requested data with not support values in its range. Fix with this version, CS141 returns now a 0 or -9999 for not available data so that error message “Illegal Data Address” is no longer displayed in Modbus client.
  • Bugfix for Astrid/Borri "Infinity" #2585
  • Bugfix fro Timeserver #2864 (timeserver changes to Greenwich time zone after a while), address 2+3 now fixed with this version
  • Bugfix for Astrid/Borri RCN Screen #2598 and communication issues with UPS Type 5,9,10,11 (#2798)

OEM customer specific features, changes and fixes

  • New customer STACO ENERGEY removes MYERS and takes it place as OEM ID 94
  • Ticket #2828 missing modbus addresses for SALICRU SLC CUBE3 added (Address 151-166)
  • Bugfix for Legrand Trimode #2605 “UPS Alert History”, fixed with this version