1.48 - 170201

1. February 2017

Normal Update

Added Features

  • Automatically logout user on password changes [#3136]
  • Automatic redirect to login page after coldboot [#3241]
  • Refresh/Reload button on "UPS Alert History" page [#3222]
  • French translations for menu and configuration pages [#3236]
  • Some german translations for menu and configuration pages [#3199]
  • Configuration option for BACS "Reverse Current Direction" [#3119]
  • BACS default threshold values based on selected module type [#3165]
  • BACS SNMP-Traps for 'Thermal Runaway' and 'Max Voltage Diff' [#3242]
  • Display of each module's HW and SW revision on BACS monitor screen [#2708]
  • Progress notification and result for restoring configuratio from backup [#3084]
  • Configuration page for RCCMD connection parameters, e.g. SSL/TLS options [#3250]
  • Documentation of alternative nut 'snmp-ups' driver command for unsupported shutdown.return [3231]
  • Event job timing parameter ranges [#3289]: delay range to 0 seconds - 1 hour and repeat interval range to 1 second - 1 day
  • Triggering of job timing parameter "At seconds remaining time" [#3217]
  • Error message in email job when entering a comma after first receiver [#3264]
  • Added Modbusvalues for Sensormanager [#2993]
    BACS VIEWER Addded Logfile export #3145, added Bargraphic #3145 + #2944
  • BACS VIEWER Automatic Report title now configurable #3013
  • BACS Addressing now up to 600 battery addresses (preparation for FW 1.54)
  • BACS Screen alignment of buttons and text #3315
  • Stringnames default at BACS changed #2854
  • Option for Firmware Update "Reset to factory settings" allows now to reset also the
    network settings #3187
  • Basic GX_R_AUX module implementation [#3062] (still functionality missing, follows with FW 1.50)

Changed Functionality

  • Event "Scheduler Shutdown" is not longer triggered [#2883]
  • Moved "RCCMD Certificate Upload" panel from System.Tools to Service.RCCMD page [#3250]
  • BACS configuration of voltage difference via drop-down box instead of edit field [#3150]
  • RCCMD job connection timeout from ~3 minutes to max. 30 seconds [#3141]

Bug Fixes

  • Error message in email job when entering a comma after first receiver [#3264]
  • Backend error 422 when starting "BACS Programmer Automatic Tool" [#3307]
  • DHCP client does not send CS141 hostname to DHCP server [#3275]
  • Configuration page System.General hangs after forcing refresh in browser [#3308]
  • Problems to display a single device event configuration with more than 10 jobs [#3073]
  • Backend chrashed after unsolicited access on UNMS TCP port 5769 [#3191]
  • User defined BACS offset and threshold configuration vales were not stored [#3228]
  • Scripted BACS module and string variables were not expanded in EventLog file [#3156]
  • Menu labels return in English following the refresh in the browser [#3237]
  • Configuring Timezone Eastern Time will cause it to be set to CST [#3213]
  • BACS "High Alarm" resets "High Warning" event [#3063]
  • Switch the BACS Temperature units to Fahrenheit does not work [#3227]
  • Missing decimal points for UPS battery voltage in monitor screen ($$PRFLEX) [#2213]
  • Broken BACS Trace tool URL [#3251] fixed with this version
  • Start of SNMP service at system boot [#2998] fixed with this version
  • Bugfix Email subject no configurable [#3218]
  • Fixed Testbutton Shutdown/Restore error message 420 [#2930]
  • Bugfix FTP Password Problem "Username or Password wrong" in BACS VIEWER fixed #3214
  • Time Server UPS internal clock synchronization only if timeserver is configured #3258
  • UNMS fixes: Double automatic Report transmission through Email fixed #3270
  • UNMS did show only 1 string, fixed with this firmware and latest UNMS
  • Error when login as guest [#3310] fixed with this version
  • Bugfix in UNMS Display Fahrenheit in Main Screen #2288
  • Bugfix in Passwort Restore function, fixed with this version #2809
  • Bugfix at manual time setting, time was lost after reboot. Fixed with this version, RTC is now
    buffered for up to 10 minutes #3178
  • Bugfix at Battery installation date #3091
  • At update from FW 1.44 to 1.46 the COM2 and COM3 configuration was lost. Fixed with this version #3051
  • Unprecise Sum voltage, Target Voltage and Current values in UNMS BACS Screen. Fix is not in
    FW 1.48 but in the UNMS, update UNMS SERVER SERVICE to Version 2.1.90, than this issue #3235 is fixed.
  • Bugfix at EVENT Jobs - if configuration was changed and the CS141 was coldbooted directly afterwards,
    the configured jobs are lost and the system is corrupted (FW update required). Fixed with this version by
    instantly writing back configuration changes in the EVENT list. [#3324]

OEM customer specific features, changes and fixes

  • PILLER: UPS time synchronization for UPS models with protocol $$PILMODn [#3258]
    • Unwanted colon in display of 'OUTPUT' value for "APOTRANS II" [#3033]
    • Display of 'Actual Time' and 'Power Faktor' for "APOTRANS II" [#3033, #3034]
    • Display of 'Tranfer count' as unsigned value for "APOTRANS II" [#3036]
    • Display of 'Phase voltages' as unsigned value for "APOTRANS II" [#3035]
    • Display of 'current' values as unsigned value for "APOTRANS II" [#3037]
    • Scrolling thru values in monitor screen for "APOTRANS II" (#3038)
    • Visualization of LED's in monitor screen for "APOTRANS II" (#3038)
  • ONLINE: UPS function screen for $$ZINTOE [#3312] added
    • Changed status colors on UPS monitor screen for "XANTO S (Mod.12)" ($$XONL12A) [#2218]
  • BENNING: Modbus mapping of UPS registers for $$BENMODn protocols [#3255]
    • Increased timeout for UPS protocols $$BENMODn [#3249]
  • CENTIEL: New XID 120, if available, is used for no. of available modules [#3206]
    • Keep fetched "UPS Alert History" lines until next reboot [#3205]
    • Use new XID 3160 to read multiple events for "UPS Alert History" [#3207]
    • Parallel handing for Status bit of protocol $$CENTIEL (#3202)
  • ALPHA: UPS monitor screen issues for "Alpha FXM" ($$ALPHAFXM) [#1919]
  • ASTRID: Configurable LEDs were always on for UPS protocol $$RCNAC [#3256]
  • ABB: Baudrate 38400 does not work for UPS protocol $$CONCE [#3100]
    • Preconfiguration of all initally as FW 1.48 and following produced CS141s will now be prepared to send out EmailTraps to ABB Switzerlands UNMS mailbox [#3265]
  • ADPOS: Fixed “Nominal Power" value on monitor screen for "Voltronic Galeon" ($$PREXT) [#2925]
    • MC115 Protocoll for ADPOS "Maxi T" communication lost alarm delayed (6 times no response)
    • Added UPS Modell "HiUp" MBSALIRM INVT Type
  • LEGRAND: Swapped page for "UPS Alert History" for protocol $$TRIMOD (#3111)
    • Fixed Autonomytime for Trimod /HE (aligning with CS121 code)#3248
  • SIEL: Custom monitor screen for $$SIELn protocols [#2609]
  • UPS setup page does not show power and load values [#3268] fixed with this version
  • POWERNET: Custom UPS screen for UPS "Powernet DAC" ($$PWRNET) [#2579]
  • CONTROLLED POWER: Function screen modifications for "EON" UPS ($$SALISEC) [#3180] and modellist changed
  • GUSTAV KLEIN: Modellist VDP_Default replaced by VDP_GKLEIN
  • DSR: Function page modifications for UPS protocol $$SALISEC (#3169)
  • GENEREX ID 12: All Transferswitches from ID 77 moved to ID 12
  • KESS: Further Changes on Battery X [#3086]
  • EATON/MGE:MGE Shut Problem bei Eaton 9PX [#3129]
  • MANNSHARD: Nominal Power added to UPSVIEW Screen
  • EFFEKTA: Adira protocol changed from CONQ to X12ONLA,B
  • INFOSEC: Added UPS Modell "Modular Mod5T" Voltronic PREXT
  • ERREPI: Added "OP 6003 R" and "OP 10003 R"
  • Customers using MITSU (Mitsubishi) protocol: Load measurings was on 3phase identical, fixed with this version [#2940]

1.46 - 161212

12. December 2016

Normal Update

Added Features

  • #3066: Attachment of UPS-Alert-History and Sensor-Logfile for eMails
  • #3184: Display of job timing event to overview column 'when'
  • #2916: Display of IP-Address and MAC-Address in BACS Screen of UNMS
  • #2684: Display of Rescue-Jumper setting for CS141MINI, CS141DMINI, CS141_R2
  • #3211, #2852: Improved wording and Layout of job editor options
  • #3178: Sync of RTC hardware in case system time is set manually
  • #3144: Verify of event job timing configuration during Fw-Update
  • Apply of BACS battery installation date when using IE web browser
  • #2801, #3215: Device added for AS400 connector on com3, AUX is now enabled/disabled thru new com3 mode
  • Preserve admin SFTP password in case of fw-update without reset

Changed Functionality

  • #3209: Improved frontend interpretation of backend error messages
  • #3210: Renamed menu item "Timeserver" to "Date & Time" and moved it under "System",
  • Renamed menu item "HTTP/SSH" to "Webserver" and moved it under "System",
  • Removed config options to enable/disable "SSH" and "SFTP" services,
  • Moved config option to enable/disable "UNMS Server" to "System"."General"
  • Moved config option to enable/disable "Auto Logout" to "System"."Webserver"

Bug Fixes

  • #3217: Major bugfix at Event job : timing option "At [x] seconds remaining time" fixed
  • #3190: Automatic use of Eventname in eMails in case subject is empty
  • #3198: False Logging of "BACS GX_R_AUX x Input x High" even if not connected
  • #3185: Fixed "Not reachable" in UNMS for following UPS protocols: $$GEDELTA, $$MDELTA, $$INFINITY, $$MGE, $$SENTR, $$SENT2, $$KLEIN1, $$GKWR1, $$GKWR3, $$GKUPS1, $$GKUPS3, $$GKNOCARD
  • #3218: Configuration of subject for email-traps and using email-trap intervall on alarms only if event has anti-event

OEM customer specific features, changes and fixes

  • PILLER: UPS monitor screen modifications for "UNIBLOCK UBR III" (#3195),
    • New images for "APOJET S II", "APOJET R II", "APOJET T II" (#3179),
    • Acknowledge of UPS internal event list items (#2988),
    • Switching powerbar on monitor screen with FF for "UBT IV" (#3002),
    • Visualization in monitor screen with FF for "UNIBLOCK UBT IV" (#3015),
    • Visualization of LED's in monitor screen for "APOTRANS II" (#3038),
    • Scrolling thru values in monitor screen for "APOTRANS II" (#3038)
  • CONTROLLED POWER: UPS function screen modifications for "EON" UPS (#3180), UPS load calculation for various "LT" UPS models changed(#3028)
  • AGIT: Screen Modifications for $$XONL12B UPS protocol(#3126)
  • LEGRAND: Logging of “Battery test result: Success” for $$ECONT/2 (#3116), Logging of “Full Test:
    • Holdtime x Min.” for $$ECONT/2 (#3116), Display of 'custom test' function button for $$ECONT/2 (#3115)
    • Swapped page for "UPS Alert History" for protocol $$TRIMOD (#3111)
  • ABB: Switch module views in UNMS for UPS protocol $$CONCE (#3148)
  • ASTRID OEM 70: Visualization in case of TRI-MONO / TRI-TRI for protocol $$EVO2 (#3189).
    • Correctdion for UPS Type 9 Display Triphase in / one Phase out
  • CET: Display of DataLog and Datalog-Chart for UPS protocol $$CET (#3159),
    • Display of "Info"-Buttons for UPS protocol $$CET, "TSI System" (#3157),
    • Visualization of AC-Output in case AC-Input is off for protocol $$CET (#3158),
    • Module info via SNMP in case modules are removed for $$CET, “TSI System" (#3157)
  • OEM ID 12: Added "THYCON UPS" model, added Ablerex Mars II, added EATON 9PX series
  • MULTIMATIC: Added HUAWEI UPS to modellist, added MD-xxxxRT series (MD_1000RT to MDO3000RT), added EATON 9PX series
  • KESS: Added "BatteryX TX301", Missing output voltage for $$MC115 (#3099), added EATON 9PX series
  • DSR: Screenchange for SALISEC protocol for "1.5 kVA Trusted UPS" and "3.0 kVA Tactical UPS"
  • EATON: added EATON 9PX series
  • SECOMP/ROLINE: added EATON 9PX series
  • MGE: MGESHUT protocol implementation improved, more tolerant than previous versions (#3129)
  • DFM SELECT and all other customers using RIELLO/AROS SENTRY protocol: UNMS triggered "not reachable" alarm at this model, fixed with this firmware (#3185)
    -ELINEX: Added Transferswitch from APC Modell ATS, added EATON 9PX series
  • Power Unlilmited Texas: added EATON 9PX series
  • AMG: added EATON 9PX series
  • PTI: added EATON 9PX series
  • AKI: added EATON 9PX series
  • SBS: added EATON 9PX series
  • CANCOM: added EATON 9PX series
  • GENESYS: added EATON 9PX series
  • ADPOS: Missing output voltage for $$MC115 and other UPS protocols (#3099)
  • DSR: Function page modifications for UPS protocol $$SALISEC (#3169)
  • CENTIEL: Parallel handing for Status bit (#3202), Timestamp in "UPS Alert History" now based on year 2000 (#3200)

1.44 - 161123

23. November 2016

Normal Update

Added Features

  • #2741: Added Sensor log and chart for SMTCOM, SMTHCOM and SENSORMANAGER
  • #2993: Added Modbus registers for sensor's
  • #3124: Added SNMP values for sensor's (SM_T_COM, SM_TH_COM, Sensorman)
  • #3168: Validation of manually configured system time
  • #3091: Added Custom configuration option for "Batteries too old"
  • #2987 + #3066: Automatic attachment of "UPS Alert History" stylesheet to EMail Job if the UPS supports this feature.
  • #3132: BACS string name configuration

Changed Functionality

  • #2245 + #2374: UPS Fulltest starts with AutonomyTime 0 and counts down BatteryCapacity

Bug Fixes

  • #2791: AUX configuration was not correctly transferred at firmware update, fixed with this version
  • #3144: Configuration of jobs was not possible using with delays. Fixed with this version
  • #3121: BACS B4 caused a script error message with UNMS and EATONs IPM, fixed with this version
  • #3087: Webpage "Refresh Time" configuration fixed with this version
  • #3103: Wrong hint for "Set System Time Manually"
  • #2996: Display of event job timing for threshold events fixed
  • #3167: "Error 520" when executing “Synchronize CS141 with Timeserver” fixed with this version
  • #3082: Frontend timeout "Error 500" during system time sync with timeserver, but time sync was OK. Timeout now increased.

OEM customer specific features, changes and fixes

  • UPS SERVIS Latvia: First version for this customers, replacing Powertronix ID 30
  • JOVYATLAS/WAERTSILA: Added Jovycube-T4S with protocol WAERTSILA (deviation from CET protocol)
  • AEG: MBCUBE Screen replaced by standard screen, this fixes wrong display of Battery capacity on this UPS
  • SALICRU: MBCUBE Screen replaced by standard screen
  • AGIT: Centralion Inova XONL12B series legend added #3128,
    • Missing SNMP values for UPS protocol $$KSTAR (#3096, \
    • #2877 added UPS Fulltest function for XONL12B, C and D
  • DFM Select and all customers using AROS SENTRY protocol:Increased "communication lost" timeout for UPS protocol $$SENT2. CS141 UPS polling changed to 6 times no correct answer before a communication lost entry is made into CS141 logfile.
  • KSTAR: Customers using KSTAR UPS did have problems with using UNMS with SNMP as communication protocol, fixed with this firmware #3096
  • ABB and LEGRAND: #3153: Message "New firmware available" is now checking against the offical download pages on GENEREX Webserver for OEMs first. If at the OEM page is a "fixed" version, than the system will not display this message, although there is a newer firmware available elsewhere. This feature is active currently for ABB OEM 36 and LEGRAND OEM 8
  • MANNSHARDT: #3138: Display of nominal power for UPS protocol $$PREXT
  • ABB and all customers using ABB OEM products: #3182 Event 'UPSMAN started' was not executed for $$CONCE
  • ABB and all customers using ABB OEM products: #3175 Display of available UPS modules for UPS protocol $$CONCE fixed
  • LEGRAND: #3114 Display of nominal power for UPS protocol $$ECONT/$$ECONT2, #3112 Display of "Switch phase On/Off" button for UPS protocol $$TRIMOD
  • PILLER: #2987 Attachment of "UPS Alert History" now configurable manually in EventJobs, #3094 Event evaluation for "UPS Output On/Off" for UPS "AP Premium"
  • ADPOS: #2977 added communication protocol for "Micro Pro V"
  • ONLINE: #2877 added UPS Fulltest function for XONL12B, C and D
  • DRS Technology : #2977 Removed "Auto Restart" and "Shutdown Type" functionality
  • COROMACTIC an all customers using SOCOMEC JBUSP protocol: #3011 Calculation of "Battery Capacity" and "Remaining Time" for $$JBUSP added
  • Multimatic and all customers using ABLEREX UPS with PRABLER2 protocol: #2995 UPS "Toggle Buzzer" function added, #2024 Missing variables for $$PRABLER2