1.62 - 171101

1. November 2017

Normal Update

Added Features

  • Added BACS Baseline Impedance % Alarm [T2936]: This makes RI impedance changes visible on the
  • BACS Webpage and warns the enduser that certain cells are drifting faster than others
  • Added BACS String-Voltage Threshold Events [T207/#3139]
  • Added STS alarm messages in statusbar [T3010] and STS wellKnownAlarms SNMP [T3058]
  • Added option for anonymous guest user authentication [T2957]
  • Added user confirmation requirement for dangerous UPS Functions [T3062]

Changed Functionality

  • Change Nominal Power menue [T2994]
  • User interface changes: Fixed menu icon widths for proper label alignment,
  • Moved 'Firmware Update' notification on top of menu, Renamed menu 'Devices > General' to 'Devices > Setup'
  • Changed Logout button to menu item and added user name to label,
  • Max. values for Event-Job enlarged [T3107]
  • Removed sending eq-off to each BACS module (only broadcast now) [T3122]

Bug Fixes

  • Degrade of BACS scan rate during discharge [T3122] - regression since 1.60
  • Battery Test logentries corrected [T2975]
  • Email-Traps deactivation [T3068]
  • Login Screen automatically scrolls below OEM-Logo [T3087]
  • BACS GX_R_AUX Outlet not available as AUX Event-Job [T3169] - regression since 1.60
  • Device 'GSMModem' at COM2 activation [T2980]
  • Display System Uptime fixed [T3099]
  • Event job dialog controls floating outside the dialog [T3075]
  • Celsius (C) is displayed when Fahrenheit is configured [T3153] - regression since 1.60
  • Scheduler job dialog controls floating outside the dialog [T3095]
  • RCCMD Broadcasts fixed [T3154]
  • If DCHP Server is unreachable booting will not completed [T2857]
  • Activation of Device AS400 caused crash of service [T3091]
  • AUX Jobs, switching AUX Port 1 and Outlet 1 fixed [T3038]
  • BACS_ALARM_COMMUNICATION_LOST shown as 'Initializing', fixed with this version [T3007]
  • BACS Communication Lost alarm Remains active when Trace says it’s communicating [T3101]

OEM customer specific features, changes and fixes

  • OEM 002: Protect Blue ($$CBSR4): Darstellungsfehler in Gesamtübersicht [T2979]
  • OEM 002: Added "Protect Flex" and "Protect PLUS M400"
  • OEM 003: APOTRANS III - Dump 2- Page ENERGY Meter Fehler [T3020]
  • OEM 003: APOTRANS III Page MAINS2 u. Load - Anzeige P-P Werte [T2919]
  • OEM 003: APOTRANS III - Dump 2- Page POWER fehlerhaft [T3019]
  • OEM 003: APOTRANS II ($$PILMOD4) Statusanzeige "0n Bypass" u. andere UPS Status [T292/#3039]
  • OEM 003: UNIBLOCK UBR II – Blindschaltbild Linien teilweise unterbrochen [T3082]
  • OEM 003: UNIBLOCK UBR II Seite „Phase“, Texte ändern [T3080]
  • OEM 003: UNIBLOCK UBR II – USV-Funktionen: Tasten-Sicherheitsabfrage, Texte ändern [T3081]
  • OEM 003: UNIBLOCK UBR II “Standard” Seite Datum/Uhrzeit anzeigen [T3079]
  • OEM 003: UNIBLOCK UBR II Led Balken fehlt im Chrome Browser [T3078]
  • OEM 003: UNIBLOCK UBR II Seite mit Batteriewerten -> Text zu lang [T3077]
  • OEM 003: UNIBLOCK UBR II – Statustexte über dem Blindschaltbild (UPS Statusbar) [T3083]
  • OEM 004: Xanto-Serie (Modell 2017): 'Site Fault' Kommando integrieren [T3106]
  • OEM 004: Screennames changed for YUNTO 450 (Mod.2017) up to YUNTO 1250
  • OEM 004: Added Voltronic NANO as YUNTO 500 -1500 Mod 2017 with $$PRECP [T2987]
  • OEM 008: DK Plus Series added
  • OEM 008: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 016: $$PWXCP Protokollerweiterung [T3094]
  • OEM 017: Changed nominal Power in VA ""MD-2000RT" and "MD-3000RT"
  • OEM 019: Changed screennames for "INVERTRONIC 1Ph" and "INVERTRONIC 3Ph"
  • OEM 022: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 025: Delta Modulon NH+, $$MDELTA, SNMP Wert upsBatteryTemperature nicht vorhanden [T3033]
  • OEM 025: Added UPS model "Fianit" with $$MBTAURUS
  • OEM 025: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 028: Added "Continuity Plus" series with $$PRABLER3
  • OEM 032: Added Centralion Transferswitch to EFFEKTA
  • OEM 032: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 033: Added SNMP Trap for EVO Alarms"A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 035: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 035: Added „JOVYSTAR-delta IB RS232“
  • OEM 036: $$CONCE: Die maximale Autonomy Time erhöhen auf 9999 Minuten [T3074]
  • OEM 036: $$CONCE: Event-jobs for SYSTEM module "CommunicationsLost" not executed [T3162]
  • OEM 038: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 044: Changed UPS modelnames "HE-PX330", "HE-PX 3120", "HE-PX 3400" to new names "HE-PX 3120 Tower", "HE-PX 3160 Modular" and "HE-PX 3600 Modular"
  • OEM 045: Added "CONVERT II series
  • OEM 047: DK Plus Series added
  • OEM 047: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 050: $$CENTIEL: UPS Monitor auch bei COM Lost Alarm anzeigen [T3072]
  • OEM 050: $$CENTIEL: Event-jobs for SYSTEM module "CommunicationsLost" not executed [T3162]
  • OEM 058: Siel EMM Multimeter, Anpassung der Werte im UPS Screen [T3120], fix network timeouts at RCCMD cascades [T2969]
  • OEM 059: Added "Continuity Plus" series
  • OEM 070: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 078: Added SLC ADAPT-X 10-90KVA
  • OEM 078: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 081: CE+T Bug Report 29.06.2017 - Sammelticket [T3031]
  • OEM 082: $$AEGSER: UPS Functions Toggle the UPS steuert die USV nicht korrekt [T3097]
  • OEM 082: SLC-80-CUBE3, $$MBCUBE2, USV Screenerweiterung der Temperaturen für Battery, Inverter und Rectifier [T3063]
  • OEM 082: Removed "SLC-700-TWIN PRO2" and changed protocol for "SLC TWIN PRO2
  • OEM 082: Added SPS ADV T series (T3002)with $$CYBEN
  • OEM 082: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad
  • OEM 095: Added SNMP Trap for EVO Alarms "A20 Overload" -> 1.3.6.1.2.1.33.1.6.3.8 upsAlarmOutputOverload and "A37 High Temperature Rectifier" -> 1.3.6.1.2.1.33.1.6.3.5 upsAlarmTempBad

1.60 - 170901

1. September 2017

Important Update

Added Features

  • BACS Device now optional for all CS141 devices with AUX/COM3 [T90/#3288].
    • This firmware changes every CS141L, SC, LM, SCM into a full qualified BACS WEBMANAGER by simply adding the BACS Busconverter and the BACS Modules
  • UPS Custom Threshold Events added [T409/#2885]
  • Watchdog OS added with Timer 5 minutes [T3009]
  • Trace Network (TCP Dump) via User Interface [T3022]

Changed Functionality

  • User interface changes: Replaced page titles above each page.
  • Moved options to en-/disable devices to new page 'Devices > General.
  • Provide uniform design and consistent structure on all dialogs.
  • Provide uniform design and consistent structure on all configuration pages.
  • Input timing parameters for all EVENT jobs increased [T89/#3289]

Bug Fixes

  • Allow backend more time to shutdown on reboot [T3024]
  • Inconsistency in Date & Time formatting for display [T2971]
  • After 1 year the uptime begins with 0 days, fixed with this version
  • Event-Logic GX_R_AUX Inputs vice-versa, fixed with this version [T2995]
  • AUX SNMP Traps added [T2960]
  • BACSKIT reboots if system time is decreased [T3046], fixed with this version
  • Event-Job Testbuttons display issues, fixed with this version [T2914]
  • AUX configuration was not transferred at firmware updates, fixed with this version [T2998]
  • BACS String Names configuration issues fixed [T2996]
  • Login as 'engineer' o. 'guest' showed false menues, fixed with this version [T2973]
  • SNMP Trap 'upsTrapOnBattery' is not repeated in 1 minute intervals [T3026]
  • Missing menue SensorLog(Chart) on COM2 fixed [T2988]
  • Backend (gxserve) hang up at overrun UPSTCP connections solved [T3016]
  • Testing command recognition of job 'RCCMD Execute' fixed [T2983]
  • Uptime in Aboutbox refresh fixed (Regression since 1.59) [T3008]

OEM customer specific features, changes and fixes

  • SBS EQUALINK: Display-Names for device and services / Equalink SBS OEM ID 69 [T2/#3410]
  • ONLINE: Minor changes on new "ZINTO 800 - 3000 VA (Mod.2017)" [T2929]
  • Implementation of new "XANTO 6000 - 20000 VA (Mod.2017)" [T2853]
  • Implementation of a new UPS series "Voltronic NANO" as YUNTO Q 2017 [T2987]
  • Bugfix XONL12A - false alarm at SNMP Variable upsAlarmWarningStatus [#3316]
  • OEM 070: Minor changes on new UPS-Protokoll UPS Type 12 einbinden [T2908]
  • WOEHRLE: Ablerex TAURUS MODBUS protocol MBTAURUS, Disable UPS OFF signal [T359/#2958]
  • AEG: Protect 3. M GRIPOW Output Current now corrected in UPS Screen [T2886]
  • Protect Plus M600 INVT/MBSALIRM Colors changed at 'On Battery' [T2921]
  • Protect Plus M600 INVT/MBSALIRM correcte AutonomyTime Display after Batterytest [T2920]
  • UPS Functionsscreens now visible again (hidden in FW 1.58) [T3005]
  • Protect Blue ($$CBSR4): Displayfix of Total Overview page [T2979]
  • PILLER : APOTRANS II values unsigned u. switching voltage problem fixed [T296/#3035]
  • AP Premium Adapter-Events [#3403] T9 & T296
  • Bugfix APOTRANS_III Events logic [T2874]
  • Screen bugfixes UBT_IV [T2902]
  • Date/Time UPS synchronization [3018]
  • APOTRANS III Page Power - Powerfactor [T2917]
  • APOTRANS III Page ENERGY Meter bugfix [T3020] and [T2915]
  • APOTRANS III Page Power - Apparent Power Anzeige [T2916]
  • APOTRANS III Page MAINS2 and LOAD - Display P-P Values [T2919]
  • APOTRANS II - Switching screen bugfixes [T47/#3356]
  • UBT_IV - Dump 41 - Screenadjustments [T2965]
  • UBT_IV - Dump 42 - Screenadjustments [T2966]
  • UBT_IV - Dump 35 – Screenadjustments [T2967]
  • APOTRANS III Page MAINS1, MAINS2 and LOAD display "neutral current" fixed [T2918]
  • $$PILMODxx: Write command at MODBUS Address 1 implemented [T45/#3358]
  • LEGRAND: Megaline ECONT2 Device Functions corrected [T2925]
  • TRIMOD Power Modules, Misc Data, Inverter/Booster Temperatures corrected [T2945]
  • DK Plus series added with 9600 baud as default [T1830]
  • TRIMOD load display over 100% causes wrong autonomytime, corrected [T2942]
  • Bugfix for TRIMOD in UNMS, now working with UPSTCP and with SNMP RFC 1628 [T2954]
  • ABB: CONCE Alarm Input Bad (XID 618) added to MODBUS Address 120 [T76/#3309]
  • SNMP upsAlarmDescriptionID counter corrected [T2922]
  • Fix at CONCE for Modbus address 167 Total battery current, shows now the values of all modules in the multidrop bus [T3037]
  • CENTIEL: UPS Events (History) Handling [ID: 10] [T152/#3204]
  • Modbus Registers 111…113 changed to 0.1Hz [T2984/ID:79]
  • Added 2 new Modbus-Register for 'Inverters Supplying the Load' (ISL) [T2985/ID:83]
  • ALTERVAC: AETSER via UPS Functions initiated shutdown/restore now fixed [T2906]
  • AGIT: KSTAR (Agpower ETX 10-500kVA Modbus) wrong status displayed without batteries, corrected [T2894]
  • $$XONL12C: Custom Screen for Agpower C RT 1-10kVA' [T36/#3370]
  • $$XONL12B: Custom Screen for 'Agpower D T 10-20kVA' [T218/#3125]
  • COROMATIC: Added new UPS models "JBUS Modulys", "JBUS Delphys MX/MP", "JBUS Delphys BC", "JBUS Statys" [T481/#2779]
  • SALICRU: Added Transferswitches "SPS 16 ATS", "SPS 32 ATS" with protocol STSABLER
  • Added modular values on INVT/ADAPT-X UPS
  • Added SLC-TWIN PRO2 and RT2 series
  • SLC TWIN PRO2 <=3kVA ($$ZINTOE), Change UPS command for Battery Voltage [T2981] and fix at Device Functions [T2978]
  • KESS: batterX Hybrid USV Implementierung [T256/#3086]
  • SNG: New OEM SNG Australia as OEM ID 77, first OEM version 77 release
  • MULTIMATIC: Added "MD-XSerie 60-125kVA"
  • Fix for EDELSTROM Functions with $$PRABLER2 Restore UPS command [T2911]
  • PowerControl UK: New OEM Powercontrol OEM ID 74, first OEM version 74 release
  • KESS: Battery X T256/#3086 fixed
  • EATON: MGESHUT at EATON UPS ID319 cause error at UPS functions, fixed
  • Eaton 9PX $$MGESHUT Server Error 503 message fixed in UPS model menue [T3028]
  • SIEL: Added custom configuration field for user data [T55/#3344]
  • EFFEKTA: Added CENTRALION Transferswitch as EFFEKTA ATS 16 [T2955]
  • INVT: Added modular values
  • CET: CE+T private MIB f. Model Agil implemented [T441/#2838]
  • ASTRID: Added new UPS-Protocol as UPS Type 12 [T2908]
  • CENTIEL: UPS Events (History) Handling [ID: 10] [T152/#3204]

1.58 - 170627

27. June 2017

Normal Update

Added Features

  • Added function to delete BACS Logfiles [T2940/T38 and #3368]
  • Added function to delete EventLog and DataLog [T92/#3286]
  • Added function for BACS Viewer to display Firmwareversion [#687]
  • Added delay of BACS Voltage Alarm after a discharge [T2863]
  • Added input of multiple IP-adresses in RCCMD Job configuration [T101/#3271]
  • Added SNMP OID for total number of modules in alarm or warning on the BACS System system Goldman Sachs [T2903]
  • Added: Support of UNMS Emailtraps for the BACS-Screen [T203/#3147]
  • Added: At AUX Job 'SensorMan Outlet' now added Logentries for Output Off [T7/#3405]
  • Added: BACS Email trap support added [T203/#3147]
  • Added: Scheduler implemented [T719/#2351]
  • Added: Function to delete BACS Logfiles [T2940]
  • Added: configurable delay of BACS Voltage Alarms after a discharge [T2863]
  • Added: SNMP OID for total number of modules in alarm or warning on the BACS System [T2903 Goldman Sachs]
  • Added: BACS support for 512 Modules and 16 Strings [T2968 + T210/#3149]

Changed Functionality

  • Changed: Protocol TOSHIBASEC (Toshiba SEC 9600b) - Add a third option for UPS efficiency value [T2927]
  • Changed: Protocol XONL12, AETSER and all other Centralion protocols, now using BT? [T31/#3376]
  • Changed: Moved 'About' menu item under 'System' and adjusted layout
  • Changed: Removed compatibility Link 'Services/Timeserver'
  • Changed: Mitsubishi 2033A,9700 protocol MITSU had startup issues, timeouts increased [T2944]
  • Changed: BACS viewer automatic report title changed #3013
  • Changed: Multiple IP-Adresses in RCCMD Jobs [T101/#3271]
  • Changed: moved 'About' menue under 'System' and adjusted layout

Bug Fixes

  • Bugfix: BACS Logfiles rotating did not work, fixed with this version [T2943]
  • Bugfix: BACS did not increase Lograte at discharge at FW 1.56, fixed with this version [T2956]
  • Bugfix: TOSHIBASEC Overload Alarm not showing up [T2860] and [T2933]
  • Bugfix: CS141 does not notify usage of HTTPS to UNMS [T37/#3369]
  • Bugfix: SNMP upsAlarmDescriptionID up-count fixed with this version [T2922]
  • Bugfix: UPS Alert history transmission through email fixed [T11/#3400]
  • Bugfix: SENSORMANAGER Events Analog Input, Digital Inputs alarm off did not work, corrected with this version [T2938]
  • Bugfix: Translations corrected [T157/#3199]
  • Bugfix: Event configuration now configurable up to 4 hours
  • Bugfix: UPS Alert history is now attached to emails [T11]
  • Bugfix: SNMP values for AUX States are wrong [T2962]
  • Bugfix: Duplicated RCCMD job receivers: regression since [1.56] [T101/T2969]
  • Bugfix: At AUX Job 'SensorMan Outlet' now added logentries for "Output-Off" [T7/#3405]
  • Bugfix: Events with GETRESULT(#-n) or GETLASTRESULT(#-n) for n!=1 fixed with this version [T2938]

OEM customer specific features, changes and fixes

  • ONLINE: Minor changes on new "ZINTO 800 - 3000 VA (Mod.2017)" [T2929]
  • Implementation of new "XANTO 6000 - 20000 VA (Mod.2017)" [T2853]
  • Bugfix XONL12A - false alarm at SNMP Variable upsAlarmWarningStatus [#3316]
  • OEM 070: Minor changes on new UPS-Protokoll UPS Type 12 einbinden [T2908]
  • WOEHRLE: Ablerex TAURUS MODBUS protocol MBTAURUS, Disable UPS OFF signal [T359/#2958]
  • AEG: Protect 3. M GRIPOW Output Current now corrected in UPS Screen [T2886]
  • Protect Plus M600 INVT/MBSALIRM Colors changed at 'On Battery' [T2921]
  • Protect Plus M600 INVT/MBSALIRM correcte AutonomyTime Display after Batterytest [T2920]
  • PILLER : APOTRANS II values unsigned u. switching voltage problem fixed [T296/#3035]
  • AP Premium Adapter-Events [#3403] T9 & T296
  • Bugfix APOTRANS_III Events logic [T2874]
  • LEGRAND: Megaline ECONT2 Device Functions corrected [T2925]
  • TRIMOD Power Modules, Misc Data, Inverter/Booster Temperatures corrected [T2945]
  • DK Plus series added with 9600 baud as default [T1830]
  • TRIMOD load display over 100% causes wrong autonomytime, corrected [T2942]
  • Bugfix for TRIMOD in UNMS, now working with UPSTCP and with SNMP RFC 1628 [T2954]
  • ABB: CONCE Alarm Input Bad (XID 618) added to MODBUS Address 120 [T76/#3309]
  • SNMP upsAlarmDescriptionID counter corrected [T2922]
  • CENTIEL: UPS Events (History) Handling [ID: 10] [T152/#3204]
  • ALTERVAC: AETSER via UPS Functions initiated shutdown/restore now fixed [T2906]
  • AGIT: KSTAR (Agpower ETX 10-500kVA Modbus) wrong status displayed without batteries, corrected [T2894]
  • $$XONL12C: Custom Screen for Agpower C RT 1-10kVA' [T36/#3370]
  • $$XONL12B: Custom Screen for 'Agpower D T 10-20kVA' [T218/#3125]
  • COROMATIC: Added new UPS models "JBUS Modulys", "JBUS Delphys MX/MP", "JBUS Delphys BC", "JBUS Statys" [T481/- #2779]
  • SALICRU: Added Transferswitches "SPS 16 ATS", "SPS 32 ATS" with protocol STSABLER
  • Added modular values on INVT/ADAPT-X UPS
  • Added SLC-TWIN PRO2 and RT2 series
  • KESS: batterX Hybrid USV Implementierung [T256/#3086]
  • SNG: New OEM SNG Australia as OEM ID 77, first OEM version 77 release
  • MULTIMATIC: Added "MD-XSerie 60-125kVA"
  • PowerControl UK: New OEM Powercontrol OEM ID 74, first OEM version 74 release
  • KESS: Battery X T256/#3086 fixed
  • EATON: MGESHUT at EATON UPS ID319 cause error at UPS functions, fixed
  • EFFEKTA: Added CENTRALION Transferswitch as EFFEKTA ATS 16 [T2955]
  • INVT: Added modular values
  • CET: CE+T private MIB f. Model Agil implemented [T441/#2838]
  • ASTRID: Added new UPS-Protocol as UPS Type 12 [T2908]
  • CENTIEL: UPS Events (History) Handling [ID: 10] [T152/#3204]