2.02 - 210930

30. September 2021

Important Update

After upgrading to this firmware version, it is no longer possible to downgrade to a lower version.

Added Features

  • User authentication using RADIUS [T566]
  • Introduce 'BACSKIT LC' series as new HW-Platform [T4542]
  • BACS Threshold "Current Difference between Strings" [T4116]
  • Include OEM specific favicon's [T4364]
  • Enable configuration of user names [T4453]
  • Introduce SNMP Test Traps for all devices [T4383]
  • Show UPS serial number in the UPS screen, if available [T4418]
  • Custom Threshold Extension Output Power/Output Load [T4410]

Changed Functionality

  • Page title changed from “CS141 Webmanager” to generic “Web Manager” [T4580]
  • Improved Company/OEM Logo, in the upper left corner of every Webpage.
  • BACS: Improve tooltip for option to Display 2 jars per module [T4366]
  • Verification of an uploaded web server TLS certificate [T4449]
  • Allow SNMP community without IP restrictions [T4436]

Bug Fixes

  • Hotfix for prior 2.02 release: “BACS E-Mail Traps may not work without GX_R_AUX” [T4578]
  • BACS Programmer Single Adressing Mode may show "failed" [T4532]
  • With option "Force HTTPS" the automatic redirection from http to https may not work [T4483]
  • GPIO: Initialize boot option and rescue pins correctly [T358]
  • At GX_R_AUX email traps generate an error [T4538]
  • After backup/restore, an upload of the server certificate is no longer possible [T4513]
  • Variable #AUTONOMTIME does not decrease during a powerfail [T4521]
  • Not possible to enter a host name for the model "SNMP UPS RFC1628 compliant" [T4472]
  • SNMPv3: The value of snmpEngineBoots is not incremented [T4520]
  • $$GPSER: Output Power Values "0" (W/VA) at 19% Load [T4487]
  • CON_R_AUX4 outputs and SENSORMANAGER outputs interfer when both devices are connected [T4198]
  • After Reboot, Rsyslog does not show the host name [T4421]
  • "SNMP UPS-RFC 1628 compliant" model = its not possible to execute a UPS test [T4422]
  • The job AUX is not available for sensormanager outputs when a BACS GXR__AUX is configured [T4197]

OEM customer specific features, changes and fixes

  • OEM 001: LEGACY version received all OPTI and CYBERPOWER UPS models
  • OEM 002: AEG added "Protect 1 (LCD)" with XONL12B
  • OEM 002: Modbus Extension AEG "Protect 8.33" [T4570]
  • OEM 003: Missing UPS History XSL File in Email attachment [T4413]
  • OEM 003: PILLER added model "AR COMFORT+"
  • OEM 004: $$PREXTXANTO (XANTO 6000 + 1Batt (Mod.2017)): Add load in percent to the UPS screen [T4540]
  • OEM 004: Xanto S 1500 (Mod.12), $$XONL12A, "Restart the UPS" button/function is not at present in the UPS Functions [T4427]
  • OEM 008: $$TRIMOD (RATP version), $$TRIMOD, all MODBUS values are zero [T4350]
  • OEM 012: GENEREX NEUTRAL added THOR ELMOD series
  • OEM 017: MULTIMATIC added "Riello Sentinel Dual SDU series"
  • OEM 022: BORRI added Galileo T/RT 1-10kVA,Leonardo T/RT 6 and 10kVA with PRABLER2
  • OEM 022: BORRI added Ingenio compact 10-20kVA with MBTAURUS
  • OEM 025: Email trap pre-configuration [T4315]
  • OEM 025: $$MBTAURUS: Wrong Output Energy Counter Calculation [T4482]
  • OEM 028: $$MBTAURUS (KRONOS 10 kVA): Add values for pos./neg. battery discharge currents [T4480]
  • OEM 028: AKKUTRONIK UPS modellist sorted new and older models moved to the LEGACY section
  • OEM 031: ALLNET added "All910019RT USB","All915019RT USB","All920019RT USB","All930019RT USB" with AEGSER
  • OEM 032: EFFEKTA added models "MD-1000-3000 PRO"
  • OEM 032: EFFEKTA cross added models "MD-4500-10000 PRO"
  • OEM 034: SCHNEIDER-ELECTRIC received FAVICON for all Webserver based products
  • OEM 035: JOVYATLAS changed UPS modelist (sorting and name adjustments)
  • OEM 036: $$CONCE: Event for the user-defined threshold alarm " Battery autonomy" could jump back and forth [T4562]
  • OEM 036: $$CONCE: Full Test runs too short via UPS functions [T4231]
  • OEM 036: $$CONCE: Provision of module data via Modbus [T4535]
  • OEM 036: ABB added "POWERVALUE 11T G2 1-10kVA" with Protocoll PREXT
  • OEM 036: ABB added "POWERVALUE 11T G2 1-10kVA" with Protocoll PREXT
  • OEM 036: ABB changed CONCE Modbus output INFREQ and BY_FREQ to integer [T4523]
  • OEM 042: COMPUPOWER SOUTH AFRICA added "Compower Micro 1 -10 kVA" using PRABLER2
  • OEM 050: $$CENTIEL(2): Modbus Extension [T4531]
  • OEM 050: $$CENTIEL(2): Massive memory loss after 7 days uptime [T4469]
  • OEM 050: $$CENTIEL(2): Provide UPS version, serial and id via Modbus [T4426]
  • OEM 050: $$CENTIEL(2): UPS Alert History: The order of CS141 and UPS display is different [T4324]
  • OEM 050: $$CENTIEL(2): UPS variables are not set correctly in email [T4454]
  • OEM 050: $$CENTIEL2: BypassBad and FanFailure are not reported to system module [T4526]
  • OEM 050: $$CENTIEL2: Power failure is sometimes not reported to system module [T4525]
  • OEM 050: CENTIEL added EssentialPower 1-20kVA
  • OEM 051: Remove UPS functions and add back custom thresholds [T4388]
  • OEM 052: First Firmware for new OEM ELIT added UPS NS & SR series 1-20 kVA
  • OEM 058: $$GPSER (SIEL UPS Safepower EVO HF): Status "batteries are disconnected" is not detected [T4473]
  • OEM 058: SIEL added "SIEL UPS Safepower EVO HF" with GPSER
  • OEM 058: SIEL added "SIEL UPS Safepower EVO HFT" with SENT2
  • OEM 058: SIEL removed UPS OFF command for Safepower EVO HF
  • OEM 058: SIEL Safepower EVO HF added "batteries are disconnected"for GPSER thru workaround - battery test results as "failed" if battery is disconnected.
  • OEM 066: AKI added APC, MGE, DELTA series
  • OEM 070: Implementation of new "Device Type 1" [T4407]
  • OEM 082: Implementation of new "SLC ADAPT2" Serie [T4316]
  • OEM 084: KOHLER added "PowerWAVE ELMOD Series"
  • OEM 085: IBR SAUDI ARABIA first Firmware release
  • OEM 087: $$MBSALIRM(HiUp series): UPS screen corrections [T4406]
  • OEM 087: $$MDELTA (Midi J D): No alarm in case of defective module [T4166]
  • OEM 087: ADPOS changed "Maxi J I series" using MBSALIRM to MBSALIRM3
  • OEM 099: AGIT added "Agpower RMY and ETC series with KSTAR2
  • OEM 099: AGIT added Agpower RMY and ETX series with MEGAE

2.00 - 210317

17. March 2021

Normal Update

Added Features

  • BACS: Add module type C41 to MIB file [T4385]
  • BACS: Improve sorting & naming in logfile list [T4286]
  • UPS $$KSTAR/$$KSTAR2: Add "Battery Test Error" event [T4323]

Changed Functionality

  • Increase login password strength [T4265]
  • Provide 3 decimal places for BACS SNMP Temperature [T4365]
  • Remove "BACS GX_R_AUX" from menu if none is configured [T3541]
  • Rename label of UPS function button "Control Output off" to "Switch Output Off" [T4187]

Bug Fixes

  • RCCMD signals do not work, if you use host names [T4395]
  • Restarting display until cold start of the CS141 [T4372]
  • UNMS BACS Screen: Dynamic impedance offset is not considered [T4332]
  • EVENT added for all Centralion XONL12C devices [T4192] [4190] Bit a55 = "Warning for Battery replace" now configurable

OEM customer specific features, changes and fixes

  • OEM 002: AEG Removed UPS model "Protect B Pro (LCD)"
  • OEM 002: AEG EVENT added for all XONL12C devices [T4192] [4190] Bit a55 = "Warning for Battery replace"
  • OEM 003: PILLER APOTRANS II<125A: Change event names of Q4/Q5 to Bypass1/2 (#0141) [T3642]
  • OEM 007: EUROTECH UPS model "Multi Sentry MST 160/200", Multi Power MPW", "Sentryum S3M 10-20", "Sentryum S3T 10-20" added
  • OEM 007: EUROTECH UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 008: LEGRANDUPS "TRIMOD HE" $$TRIMODHE, UPS Event History is not working [T4320]
  • OEM 008: LEGRANDUPS model "KEOR Compact" with $$MBTAURUS added
  • OEM 008: LEGRAND UPS model ""TRIMOD HE Profibus" added to make it compatible to Profibus-Adapter
  • OEM 012: GENEREX NEUTRAL added "Micropower series" $$PRFLEX
  • OEM 017: MULTIMATIC added "Huawei UPS2000-G" , "MD-6000T 6kVA/6kW", ""MD/MDO PRO Series"
  • OEM 021: ERREPI UPS model "SENTRYUM", "SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 026: CTA UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 028: AKKUTRONIK UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 034: SCHNEIDER-ELECTRIC added "APC Easy UPS 3L/3M" $$MBSALIRM INVT
  • OEM 035: JOVYATLAS UPS "JOVYSTAR-PLUS-E-RS232" $$EVO2: SNMP Values/USV-Screen Discrepancies [T4312]
  • OEM 036: ABB $$CONCE UPS: Provide serial number via Modbus [T4304]
  • OEM 036: ABB $$CONCE, Custom Threshold "Outputpower greater than" is not working [T4216]
  • OEM 036: Rollback: ABB $$CONCE: Extend Mains and Bypass Frequencies by decimal digits [T4253]
  • OEM 039: KAMIC UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 048: TRIATHLON UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 053: CPS UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 055: COROMATIC changed "JBUS Statys" $JBUSSTATYS [T481] and [#2779]
  • OEM 057: BRITISH POWER CONVERSION added EMERGENCY LIGHTING System "PowerPro ELMOD" $$BPC_ELMOD
  • OEM 058: SIEL $$MEGAE added to the 'SIEL_TRAPMSG' feature [T3377]
  • OEM 058: SIEL UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 059: ALPHA ATS-16/32 added
  • OEM 059: ALPHA added "Continuity-Plus-2000S-3000S", "TRI-Power X33KE 10-40kVA, "TRI-Power X31SE ACT/EXT, "TRI-Power X33SE ACT 10-20kVA" 
  • OEM 060: DFM SELECT UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 061: SAPOTECLIA UPS model "Master MPS Serie" added
  • OEM 064: LEISTUNG BRAZIL UPS model"SENTRYUM", "SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 065: ELINEX added "Centiel EssentialPower" $$PRABLER2
  • OEM 070: ASTRID added "UPS Typ 18"
  • OEM 071: INFOSEC added "E4 PRO ONE" and "E7 ONE RT"|$$2400N81|$$PREXT
  • OEM 072: E-TEC UPS "ER 300 T", $$SENT2, UPS event history not working [T4360]
  • OEM 074: TWIN-SOURCE added DCC-I ATS and added an new BACNET-Section for "TwinSource DCC-I ATS", "TwinSource DCC-II STS", "TwinSource DCC-III STS"
  • OEM 077: SNG AUSTRALIA UPS model "SENTRYUM","SENTRYUM XTEND-XTD", SENTRYUM COMPACT-CPT" ,"SENTRYUM ACTIVE-ACT" added
  • OEM 078: SICOTEC Logo changed
  • OEM 055: SICOTEC changed "STATYS" $$JBUSSTATYS" [T481] and [#2779]
  • OEM 082: SALICRU added SLC CUBE 4 >=30kVA
  • OEM 084: KOHLER UPS "PW3000P1 10kVA" and "PW3000P1 20kVA" with $$PREXTCRC added
  • OEM 086: ENEDO Name change to ENEDO and UPS "Enedo DAC" added
  • OEM 087: ADPOS modellist new arranged
  • OEM 090: UPS "91RT 1000", $$AETSER: Output values are not displayed in the UPS screen [T4357]
  • OEM 095: STATRON Logo changed
  • OEM 095: STATRON added BENNING Enertronic I as Statron S3100 and S3300

1.98 - 201224

24. December 2020

Normal Update

Added Features

  • Add RCCMD variables to the parameters of the Job EMail [T3785]
  • BACS Threshold "Current Difference between Strings" [T4116]
  • Offer option for simultaneous use of "MODBUS over TCP" and "RS485" [T4287]
  • Option to Display 2 Jars per Module on BACS Monitor for Nicd Batteries [T4049]

Changed Functionality

  • Hide Energy Meter Page if no data available [T4233]
  • Increase BACS Voltage Threshold range for the low Alarm [T4266]
  • Configuring the RCCMD job "Shutdown" as broadcast requires the entry of an IP subnet [T4191]
  • Change email option "send copy on all emails" to "automatically send an email on important" events

Bug Fixes

  • Rsyslog: In case of network errors the communication to the server is interrupted [T4288]
  • The configured host name does not appear within the DHCP server [T4251]
  • bacsAlarmsPresent variable does not change after alarms clear [T4297]
  • Archived Datalog contains only the current Datalog values after download [T4273]
  • $$PREXT: Implementation of new Voltronic Multidrop Protocol [T4151]
  • Rsyslog sender should send configured host name [T4260]
  • $$KSTAR: Invalid value for not connected Ambient Temperature Sensor [T4215]
  • BACS: Round display of dynamic impedance thresholds to 2 decimal places [T4309]
  • The same parameters should be available for the scheduler email job as for the event email job [T4308]
  • Rsyslog does not send messages in case of the CS141 reboots without a valid syslog server [T4313]

OEM customer specific features, changes and fixes

  • OEM 002: Removed UPS model Protect B Pro (LCD) [T4045]
  • OEM 003: Remove UPS Monitor Screen for Model "IP-Control" and "IP-Master Control" [T4249]
  • OEM 004: $$PREXTXANTO, UPS Functions: Its not possible to switch the UPS on [T4234]
  • OEM 004: $$PREXTZINTO, UPS Functions: Its not possible to switch the UPS on [T4232]
  • OEM 007: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 008: Added "KEOR Compact" using protocol $MBTAURUS from ABLEREX 
  • OEM 012: Added "micro 12VDC/24VDC/48VDC" protocol PRFLEX
  • OEM 012: Added "Kronos" series from ABLEREX
  • OEM 017: Added UPS Modell "MD-6000T 6kVA/6kW" and "HUAWEI UPS2000-G"
  • OEM 017: ML-T 800, $$PREXT, display of the nominal power is not correct [T4322]
  • OEM 021: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 022: Event added for UPSTYP 5 "A35 Diesel Mode Off"
  • OEM 026: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 028: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 028: UPS Custom Threshold Extension $$MBTAURUS [T4298]
  • OEM 032: Workaround for missing batterypack at Adira implemented
  • OEM 034: Added protocol "APC Easy UPS 3L/3M" as OEM version from INVT protocol $$MBSALIRM
  • OEM 035: JOVYCUBE-T4S, $$WAERTSILA, the value of the battery current is not at present via SNMP [T4292]
  • OEM 036: $$CONCE: Extend Mains and Bypass Frequencies by decimal digits [T4253]
  • OEM 038: Event added for UPSTYP 5 "A35 Diesel Mode Off"
  • OEM 039: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 041: EVEREST Triera ETR33100, $$PRPYRDSP, UPS screen is not displayed correctly [T4226]
  • OEM 048: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 050: $$Centiel UPS "Not reachable" in UNMS [T4252]
  • OEM 050: $$CENTIEL, SNMP values for input frequency phase 2 and 3 are not at present [T4228]
  • OEM 051: Mitsubishi 1100A additional fault codes [T4317]
  • OEM 053: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 055: $$JBUSP, Battery Bad should be displayed at screen [T4284]
  • OEM 055: MASTERYS GP4 10-40, $$JBUSMODULYS, some measurements are displayed faulty [T4294]
  • OEM 055: Added SOCOMEC modular protocol and name "JBUS Statys" using protocol $JBUSSTATYS
  • OEM 057: Implementation "EL MOD" [T4160]
  • OEM 058: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 059: Added "Continuity-Plus", "TRI-Power X33KE 10-40kVA", "TRI-Power X31SE ACT, EXT series
  • OEM 060: DFM SELECT - Added UPS Model "SENTRYUM" using $GPSER
  • OEM 062: With a single-phase rectifier, the DC output current of the rectifier is displayed at the AC current values [T4244]
  • OEM 064: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 065: Elinex UNMS/CS141 Diesel Generator Implementation [T3933]
  • OEM 065: Added "Centiel Essential Power"
  • OEM 066: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 070: Implementation of new "UPS Type 17" [T4272]
  • OEM 070: Implementation of new "UPS Type 18" [T4302]
  • OEM 070: Event added for UPSTYP 5 "A35 Diesel Mode Off"
  • OEM 071: Added "E4 PRO ONE" with protocol $$PREXT and "E7 ONE RT"
  • OEM 077: Added UPS Model "SENTRYUM" using $GPSER
  • OEM 078: STATYS added using protocol $JBUSSTATYS
  • OEM 082: New Salicru SLC CUBE 4 >30KVA Modbus IN72602 [T4202]
  • OEM 082: $$MBCUBE2: New functions and jobs: "Switch UPS To Bypass", "Switch Load To Inverter/Online Mode" [T4291]
  • OEM 095: Screen modifications "Statron S3100 UPS/Statron S3300 UPS" [T4271]